Summary of Contents for Philips SpaceWice

  • Page 2: Table Of Contents

    FCC Compliance Statement ......................40 Warranty ............................40 Technical support ..........................40 This document should only be used for commissioning a SpaceWise Office System. For Industrial applications, please refer to the commissioning manual of SpaceWise for Industrial Applications. Philips Lighting North America...
  • Page 3: Spacewise Technology Luminaire

    3.7 1. SpaceWise Technology Luminaire Philips luminaires with wireless SpaceWise Technology are stand-alone LED lighting systems with integrated occupancy sensing and daylight harvesting, designed specifically for office spaces. Automated dimming behaviors are activated after installation using a SpaceWise remote control to create groups and connect wireless switches.
  • Page 4: Spacewise Technology Luminaire Sensor Coverage Area

    The shield is a plastic circular ring located around the occupancy sensor lens. To install the shield, first pull out the ring completely and then reinsert it backwards so that the elongated part of the shield is facing downwards. Philips Lighting North America...
  • Page 5: Layout

    Smaller groups may turn off more frequently than desired. Install luminaires per manufacturer installation instructions and ensure sensors from adjacent luminaires are not positioned next to one another. Philips Lighting North America...
  • Page 6: Spacewise Remote (Irt 9090)

    The angle under which the IR receiver in the sensor will receive signal is a 55 degree angle. PREPLAN WHICH FIXTURES YOU'LL WANT TO BE IN A GROUP, AND TRY TO ANSWER QUESTIONS BEFORE STARTING SO YOU CAN COMPLETE & LOCK WITHOUT DISTRACTIONS. Philips Lighting North America...
  • Page 7: Grouping

    “add.” Repeat step for adding all the luminaires in the group. Point to any of the luminaires added in All the luminaires in the group the group and press “close.” will go to 50% light level. Philips Lighting North America...
  • Page 8 Refer to the FAQ section for additional information on how to correct non responsive luminaires. Philips Lighting North America...
  • Page 9: Application Modes

    Various application modes are supported within SpaceWise Technology. Since behavior varies for each mode so it is recommended to select the mode that closely reflects the installed application space. See the SpaceWise Design Guide (www.philips.com/spacewise) for details. Application ON/OFF behavior...
  • Page 10: Application Mode Selection

    Red LED on remote will start group and press “mode.” blinking. While the LED is still blinking red, enter Red LED on remote will stop the number for the preferred mode (see blinking. list at step 5). Philips Lighting North America...
  • Page 11 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 12: Maximum Light Output Selection

    Red LED on remote will stop Wait for LED to stop blinking (apx. 10 blinking. seconds). The luminaire will FLASH twice Point remote to any of the luminaires and group light level will go to and press “send.” 50%. Philips Lighting North America...
  • Page 13 50% light level to permanent 77% light level. If you repeat the step down sequence again then upon careful observation you will see the subtle change in light level from 77% to 66%. Philips Lighting North America...
  • Page 14 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 15: Activate / Deactivate Occupancy Sensor

    Red LED on remote will start blinking. While the LED is still blinking red, enter Red LED on remote will stop the numbers: blinking. “10”: Enable occupancy sensing “12”: Disable occupancy sensing (lights will stay at 100%) Philips Lighting North America...
  • Page 16 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 17: Activate / Deactivate Daylight Sensor

    50%. Press “daylight” button. Red LED on remote will start blinking. While the LED is still blinking red, enter Red LED on remote will stop the numbers: blinking. “1”: Disable daylight sensing “2”: Enable daylight sensing Philips Lighting North America...
  • Page 18 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 19: Manual Daylight Calibration

    When the arrow keys are and adjust the group light level to the pressed, red LED on remote will required level using the dimming “up” or keep blinking. “down” arrow keys The group will dim up or down accordingly. Philips Lighting North America...
  • Page 20 Point to any of the luminaires in the Red LED on remote will start group and press “lock.” blinking. The luminaire will FLASH twice. Wait for LED to stop blinking (apx. 10 Group is ready for normal seconds) then press “send.” operation. Philips Lighting North America...
  • Page 21: Test Occupancy Coverage Area (Walk Test)

    Point remote to any of the luminaires Test feature is activated; users and press “test.” can now walk in the space to estimate the occupancy coverage area. To stop the test feature, press the “test” button again. Philips Lighting North America...
  • Page 22: Path Of Egress Mode For Emergency Applications

    27% will be delivered. SpaceWise luminaires can also be ordered with a Philips emergency driver option . If this configuration is purchased then luminaires don’t have to be configured as “path of egress”...
  • Page 23 Red LED on remote will start blinking. While the LED is still blinking red, enter Red LED on remote will stop the numbers: blinking. “11”: Enable path of egress feature “10”: Disable path of egress feature Philips Lighting North America...
  • Page 24 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 25: Troubleshooting

    Luminaire will turn OFF and then Once LED stops blinking, with remote turn back ON to indicate reset. still pointing to the luminaire in the group, press “send.” Repeat step “b” for all the luminaires that need to be reset. Philips Lighting North America...
  • Page 26: Linking A Wireless Switch To The Spacewise Group

    Point remote to any luminaire and press Wait for the luminaire to dim “Open,” once. down to 5%. Make sure the button is pressed only once. Pushing multiple times can create multiple networks which can cause undesired operation. Philips Lighting North America...
  • Page 27 “d” then repeat step “d” but with a the luminaire will FLASH twice different button (1) this time. If switch and group light level will go to has joined the group then go to step “f.” Philips Lighting North America...
  • Page 28 “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Philips Lighting North America...
  • Page 29: Linking A Wireless Scene Selector To The Spacewise Group

    Red LED on remote will stop Wait for LED to stop blinking (apx. 10 blinking. seconds). The luminaire will FLASH twice Point remote to any of the luminaires and group light level will go to and press “send.” 50%. Philips Lighting North America...
  • Page 30 “c” but with a different button (1) this FLASH twice and group light level time. If scene selector has joined the will go to 5%. group then go to step “e.” Philips Lighting North America...
  • Page 31 OFF and ON seconds) then press “send.” once for Daylight calibration. Group is ready for normal operation. Test the scene selector by pressing the All the luminaires in the group buttons. will react to the button action. Philips Lighting North America...
  • Page 32: Linking An External Wireless Ceiling Sensor To The Spacewise Group

    Red LED on remote will stop Wait for LED to stop blinking (apx. 10 blinking. seconds). The luminaire will FLASH twice Point remote to any of the luminaires and group light level will go to and press “send.” 50%. Philips Lighting North America...
  • Page 33 Red LED on remote will start group and press “lock.” blinking. The luminaire will FLASH twice Wait for LED to stop blinking (apx. 10 and group will turn OFF and ON seconds) then press “send.” once for Daylight calibration. Philips Lighting North America...
  • Page 34: Creating Zones In A Group

    Red LED on remote will stop Wait for LED to stop blinking (apx. 10 blinking. seconds). The luminaire will FLASH twice Point remote to any of the luminaires and group light level will go to and press “send.” 50%. Philips Lighting North America...
  • Page 35 All the luminiare in the selected zone will go to 50% while the and press the “right arrow” key. luminaires in the other zone will go to 5%. Press the right arrow key again to move to verify the next zone. Philips Lighting North America...
  • Page 36 “zone”. The entire zone turns on or off accordingly. Point to the same luminaire and press “on” or “off.” To stop the test process, point to the same luminaire and press “close.” Philips Lighting North America...
  • Page 37: Altering The Default Scenes On The Scene Selector (With No Zones)

    Select number “2” to store the scene on the “.” (bottom left) button on the scene selector. Select number “3” to store the scene on the “. .” (bottom right) button on the scene selector. Philips Lighting North America...
  • Page 38: Altering The Default Scenes On The Scene Selector (With Zones)

    Point remote to the same luminaire and The zone will dim or switch dim the zone to the required light level accordingly. by pressing the “up” or “down” arrow keys or switch the zone on/off via the “on” or “off” buttons. Philips Lighting North America...
  • Page 39 Point to any of the luminaires in the The luminaire will FLASH twice. group and press “save.” Test the scene selector by pressing “.” All the luminaires in the group and/or “. .” buttons. will react to the button action. Philips Lighting North America...
  • Page 40: Faqs

    D. Do my luminaires forget their settings after power is lost or interrupted? No, all settings are retained as long as the luminaires have not been factory reset or there has been a hardware failure. Philips Lighting North America...
  • Page 41: Fcc Compliance Statement

     This luminaire must accept any interference received, including interference that may cause undesired operation Any changes or modification not expressly approved by Philips could void the user’s authority to operate this equipment. This product is intended for commercial use only.
  • Page 42 SpaceWise for Office Applications v. 3.7 Philips Lighting North America...

Table of Contents