11. System is on but,
no-thing is operating.
The blower is off.
Rev. 01
05/27/2016
Problem
No air flow, fire stat,
water on floor or
smoke detector alarm
is activated.
Page 37 of 42
Symptom
The display shows
one or more of these
alarms and the Alarm
LED is on.
Action
connections are
secure and that
contactors do not
chatter when switch-
ed. Check that the
sys-tem ground is
properly connected to
an earth ground.
The system is
automatic-ally shut
down if any of these
conditions occur.
Determine what the
cause is and remedy.
Then, press the Reset
button on the MCP.