clearances to
combustibles
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance and
the chimney connector. The farthest distance is
correct if the two clearances do not coincide.
For example, if the appliance is set as indicated in
one of the figures but the connector is too close,
move the stove until the correct clearance to the
connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood floor. This unit can also be
installed directly on carpeting or vinyl.
Use the minimum clearances shown in the dia-
grams below:
RC500E Clearances
A
Left/Right Side Wall to Unit*
B Back Wall to Unit
C Vertical Vent Pipe
to Back Wall
D Wall to Centerline of Pipe
E Unit Corner to Wall (Top Vent) 4" / 50 mm
Unit Corner to Wall (Rear Vent) 5-3/4"/146 mm
F Alcove Width
G Alcove Depth
H Minimum Ceiling from
top of unit
*IMPORTANT
If installed in an alcove the clearance on one side
must be a minimum of 9 inches. The other side
would need to be a minimum of 21 inches as a
result of the clearance being 50 inches in length
when installed in an alcove.
If the minimum of 9 inches is increased on one side,
the other side could be decreased if the alcove
was 50 inches.
Left Side Wall
Left Side Wall
F
Horizontal
Pipe
F
Right Side Wall
Right Side Wall
D
locating your
gas stove
When selecting a location for your stove, ensure
that the clearances listed above are met as well
as ensuring that there is adequate accessibility
for servicing and proper operation.
A)
Cross Corner
B)
Room Divider
C)
Island
D)
Flat on Wall
E)
Flat on Wall Corner
F)
Flush with Wall/Alcove
For Vent Termination requirements, see "Exterior
9" / 229 mm
Vent Terminal Locations" section.
2" / 50mm
**Maximum length will vary depending on vent run.
See complete details in this manual.
2" / 50 mm
8-3/4"/222 mm
manufactured mobile home
additional requirements
50" / 1270mm
1. Ensure that structural members are not cut or
36" / 914mm
weakened during installation.
2. Ensure proper grounding using the #8 ground
15" / 381mm
lug provided.
3. Appliance must be anchored to the floor
with the supplied anchoring methods.
combustion and
ventilation air
The combustion air from this appliance is drawn
from outside the building through the outer flue.
Extra provision for combustion air inside the
room is not required.
flue pipe
Vertical

clearances to combustibles

Pipe
Horizontal top =
Horizontal sides =
G
Horizontal bottom = 2"
Vertical =
H
Passing through wall/floor/ceiling
when fire-stop is used = 1-1/2"
tooltip
B
**20'
12'
E
Max.
F
C
A
D
3"
2"
2"
installation
accent light bulb
install
Accent light bulbs are packed in the manual
pack.
1. Lift off cast top and place on a soft surface.
2. Remove 4 screws from each light assembly
housing in locations shown below.
Top of Unit
3. Lift housing off unit to replace bulb.
Note: Do not touch bulb with bare hands, use gloves
or a tissue to handle bulb.
4. Reinstall 4 screws to secure each housing.
5. Reinstall cast top.
RC500E |
25