Regency P42 Owners & Installation Manual

Gas fireplace
Hide thumbs Also See for P42:

Advertisement

P42 Gas Fireplace
WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
918-523b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
MODELS: P42-NG4 Natural Gas P42-LP4 Propane
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
Installation Manual
www.regency-fi re.com
FOR YOUR SAFETY
What to do if you smell gas:
 Do not try to light any appliance
 Do not touch any electrical switch:
do not use any phone in your
building.
 Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
 If you cannot reach your gas
supplier, call the fi re department.
Owners &
07/30/09

Advertisement

Table of Contents
loading

Summary of Contents for Regency P42

  • Page 1 Owners & P42 Gas Fireplace Installation Manual www.regency-fi re.com MODELS: P42-NG4 Natural Gas P42-LP4 Propane WARNING: FOR YOUR SAFETY If the information in these instructions are not followed exactly, What to do if you smell gas:  Do not try to light any appliance a fi...
  • Page 2 WARNING HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
  • Page 3 P42 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P42 has been approved by Warnock Hersey for both safety and effi...
  • Page 4: Table Of Contents

    Aeration Adjustment ............25 Brick Panels..............25 Log Set Installation ............26 Standard Flush Door ...........27 Flush Louvers ..............27 Double Screen Doors ..........27 Optional Bay Door ............28 Bay Louvers..............28 Full Screen doors ............29 Wiring Diagrams ............32 ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 5: Safety Label

    SAFETY LABEL This is a copy of the label that accompanies each P42 Zero Clearance NOTE: Regency ® units are constantly being improved. Check the label Direct Vent Gas Fireplace. We have printed a copy of the contents here on the unit and if there is a difference, the label on the unit is the correct for your review.
  • Page 6: Requirements

    (e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 7: Installation

    fi ring correctly and operation fully explained YOUNG CHILDREN SHOULD BE to customer. CAREFULLY SUPERVISED WHEN 13) Do not slam shut or strike the glass door. THEY ARE IN THE SAME ROOM AS THE APPLIANCE. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 8: Manufactured Mobile Home Additional Requirements

    ADDITIONAL OPTIONAL 4) The P42 Direct Vent Gas Fireplace can be REQUIREMENTS HEAT RELEASE KIT installed in a recessed position or framed out into the room as in A, B, C, D. See Diagram...
  • Page 9: Clearances

    K i t h a v e d i ff e r e n t clearance and framing requirements, check Heat Release Kit the HeatWave and Heat Maximum Release manual for 1-1/2" projection at 2" details. minimum clearance. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 10: Framing And Finishing

    INTRODUCTION 1) The top standoffs are shipped installed. The P42 uses the "balanced fl ue" technology 2) The Top Facing Support and the 2 Side Co-Axial system. The inner liner vents products Nailing Strips can be installed at different of combustion to the outside while the outer depths depending on the width of your facing.
  • Page 11: Exterior Vent Termination Requirements

    * Clearance in accordance with local installation codes and the requirements of the gas supplier 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly 3 feet (91cm) above - if within 10 feet (3m) horizontally ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 12: Venting

    ® Direct Vent system (Flex) a) Liner sections should be continuous without any joints or seams. # 946-516 includes all the parts needed to install the P42 with a b) Only Flex pipe purchased from Regency ® may be used for Flex maximum 10' run.
  • Page 13: 4" X 6-5/8" Rigid Pipe Cross Reference Chart

    Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI. 4 X 6 5/8 RIGID PIPE CROSS REFERENCE CHART Components from different Manufacturers may not be mixed. Not all rigid pipe components are available directly from Regency. Description...
  • Page 14 Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination. Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 15: Rigid Pipe Venting

    The Rigid Pipe Venting System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish. We recommend using the galvanized fi nish for installation with the P42.
  • Page 16: Horizontal Terminations

    • Horizontal vent must be supported every 3 feet (0.9 meter) • Firestops are required at each fl oor level and whenever passing through a wall Note: Regency ® Direct Vent System (Flex) is only approved for horizontal terminations. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 17 3 feet • Firestops are required at each fl oor level and whenever passing through a wall. Note: Regency ® Direct Vent System (Flex) is only approved for horizontal terminations. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 18: Vertical Terminations

    (Propane & Natural Gas) The shaded area in the diagram shows all allowable combinations of straight vertical and offset The P42 is approved for a 37 ft. (11.3m) straight to vertical terminations with rigid pipe vent systems for Propane and Natural Gas.
  • Page 19 INSTALLATION The P42 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset The P42 is approved for a 37 ft. (11.3m) straight using two 90 elbows (two 45 elbows equal one 90 elbow) with rigid pipe vent systems for vertical, with rigid pipe vent systems for Propane Propane and Natural Gas, as per the diagram below.
  • Page 20 946-563 that clearances to combustibles are Air Intake maintained. Pipe Length Co-Linear Flex Adapter with Kit# Rigid Pipe Adapter 946-563 # 510-994 90 Degree Elbow Inner Pipe Adapter with Kit# 946-563 ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 21 INSTALLATION VENTING ARRANGEMENTS - VERTICAL TERMINATIONS with Co-linear Flex System for both Residential & Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 22 “Mill-Pac” sealant (supplied) to every in- local code requirements. ner pipe connection. Failure to do so may result in drafting or performance issues not Diagram 4 covered under warranty. Silicone (red RTV) is optional. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 23 Diagram 3 and install the height requirements specifi ed in Diagram 5 or fi restop. local codes. Note that for steep roof pitches, Diagram 6 the vertical height must be increased. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 24: Installation Procedures

    Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 25: High Elevation

    1) Make sure the valve is in the "OFF" position. 2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" (3mm) wide fl at screwdriver. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 26: Aeration Adjustment

    fl at up against the wall, they should fi t snugly against the top of the fi rebox. Diagram 3 (front) IMPORTANT: Dangerous operating conditions may occur if the panels are broken. (back) ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 27: Log Set Installation

    Burner tray without front logs in place PROPANE IMPORTANT Completed Log Set Installation For Propane Units - only place rockwool and platinum embers on the rear burner tray behind the burner tube. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 28: Standard Flush Door

    See diagram 3. Clip installed on right side. Diagram 3 NOTE: Springs must always be OVER not under the gas line. To remove the fl ush door, reverse the above steps. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 29: Optional Bay Door

    1 screw on each end. 3) Slide the valve extension knobs onto the valve knobs. 3) Secure to the fl ush door bottom bracket with 2 screws provided. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 30: Full Screen Doors

    Also remove the center screw. Inside Top of Outer Frame Screw Screw Full Screen Door Frame Screw Cut-Out Oblong Hole Cut-Out Flange Bottom Flange Backside of Full Screen Door Frame Shown Cut-Outs ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 31 2x #8 Self Tapping Bracket Right Side Philips Screws per hinge. of Bottom Grill 7) Re-install Glass Door. Refer to the manual for instructions. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 32 NOTE: Failure to install the doors in the fully open position could result in paint damage to the surface of the door. Hinge Top Grill Screen Door 10) Close screen doors. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 33: Wiring Diagrams

    Power IN when servicing controls. Millivolt Wires Wiring errors can cause improper and dangerous operation. 4-7/16" 1-1/2" 5-1/2" ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 34 INSTALLATION PROPANE Units and Units Equipped with DC Spark Boxes ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 35: Operating Instructions

    "Copy of Lighting Plate Instruc- tions" section for more details. IMPORTANT: Gas on/off knob cannot be turned from "PILOT" to "OFF" unless it is partially depressed. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 36: Copy Of The Lighting Plate Instructions

    3) Turn off all electric power to the appliance if service is to be performed. You may shut off the pilot during prolonged non use periods to conserve fuel. DO NOT REMOVE THIS INSTRUCTION PLATE 918-474b ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 37: Maintenance

    "whisper" sound. Gas Control Valve: As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 38: Gold-Plated Louvers

    REPLACEMENT Bay Glass Replacement The 24 carat gold-plated fi nish on the louvers Your P42 fireplace is supplied with high and trim requires little maintenance, and need 1) Remove the door from the unit and place temperature, 5 mm Neoceram ceramic glass only be cleaned with a damp cloth.
  • Page 39: Removing The Fan

    Hint: If you are using black pipe, ensure that there is a union by the valve, otherwise removal will be almost impossible. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 40: Installing Valve

    Note: Failure to install a new gasket may severely affect the 15) Reinstall the vermiculite, embers, rockwool and logs as needed. appliance performance. 16) Install and close the door and replace the louvers. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 41: Parts List

    Junction Box 946-570 Heat Release Duct Kit (Optional) 125) 910-165 Fan (120 V) 126) 946-000 Flexible Air Release Duct 127) 690-022 Cover Plate 918-523 Manual *Not available as a replacement part. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 42: Burner & Log Assembly

    Air Shutter Gear Assembly - Female 904-565 Hex key 3/16" AF 600-964 P42 Log Set 910-421 Pilot ON/OFF Extension Knob (with Bay Front) 910-422 HI/LOW Extension Knob (with Bay Front) *Not available as a replacement part. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 43: Flush Door & Louvers

    Door Latch Assembly Pushnut Fastener Screw 6-32 x 5/16 Pan Head Washer #6 External Star 187) 904-712 U-Clip for Screen Door ® 188) 948-216 Regency Logo Plate *Not available as a replacement part. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 44: Bay Front & Louvers

    Flush Glass Retainer Bracket 113) * Bay Door Trim (Each) -Black 122) 948-216 Regency ® Logo Plate 602-932 Bay Door Trim (Set) - Gold * Not available as a replacement part. ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 45 NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 46 NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 47 NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ® Regency P42-4 Zero Clearance Direct Vent Gas Fireplace...
  • Page 48: Warranty

    It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect. The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers.
  • Page 49 Fireplace Products International Ltd. is pleased to extend this Limited Lifetime Warranty to the original ® purchaser of a Regency Product. See the inside back cover for details. ® Register your Regency online at http://www.regency-fi...

This manual is also suitable for:

P42-ng4P42-lp4