Tab.68
Parameter
Description
HP058
Enabling Heat pump Silent mode
HP094
Start time of the low noise when option activated
HP095
Stop time of the low noise when option activated
7685645 - v04 - 07032018
3. Choose the contact directions of the BL1 IN and BL2 IN multifunc­
tion inputs by setting the AP098 and AP099 parameters.
Tab.66
Parameter
Description
AP098
Blocking input 1 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
AP099
Blocking input 2 contact direction configuration
0 = input active on Open contact
1 = input active on Closed contact
4. Configure the temperature offsets for the voluntary overheating by
configuring the HP091 and HP092 parameters.
Tab.67
Parameter
Description
HP091
Offset temperature of heating setpoint when
photovoltaic function is activated
HP092
Offset temperature of DHW setpoint when
photovoltaic function is activated

10.5.12 Reducing the noise level of the outdoor unit

Silent mode is used to reduce the noise level on the outdoor unit during a
given time range, particularly at night. This mode gives temporary prece­
dence to silent running rather than temperature control.
Important
Silent mode only operates if the silent running kit is connected
to the outdoor unit.
This package is not compatible with the AWHP 4.5 MR outdoor
unit.
Silent mode is managed by the following parameters which can be found
in the Installer menu, EHC–04, ADV:

10.5.13 Detecting an additional or replacement PCB

The automatic detection function is used if a control PCB has been re­
moved, replaced or added.
1. Go to the Installer menu.
2. Access the Installer menu by entering the code 0012 by pressing the
and
keys.
3. Confirm access by pressing the
4. Select the EHC–04 main PCB by pressing the
5. Confirm the selection by pressing the
10 Settings
key.
or
key.
key.
AWHP-2 iMPI
97