4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS
4.1 - Physical data 30XBP (continued)
30XBP-850 to 1500 (continued)
30XBP
Capacity control
Minimum capacity
Air heat exchanger
Fans
Standard unit
Quantity
Maximum total air flow
Maximum rotation speed
Unit + option 15LS
Maximum total air flow
Maximum rotation speed
Water heat exchanger
Water volume
Max. water-side operating pressure without hydraulic module
Hydraulic module (option)
Pump
Expansion vessel volume
Max. water-side operating pressure with hydraulic module
Water connections without or with hydraulic module
Connections
External parameter
(5)
Casing paint
(5) Depends of options.
24
850
900
1000
Touch Pilot, , Electronic Expansion Valve (EXV)
%
15
15
15
Aluminum micro-channel coils (MCHE)
FLYING-BIRD 6, axial fan with rotating impeller
14
14
16
l/s
67480
67480
77120
r/s
15,7
15,7
15,7
l/s
55020
55020
62880
r/s
11,7
11,7
11,7
l
119
130
140
kPa
1000
1000
1000
Pump, Victaulic screen filter, relief valve, water and air drain valve,
pressure sensors, expansion tank (option)
Centrifugal pump, monocell, 48,3r/s, low or high pressure (as required), single or dual
inch
mm
inch
6
6
mm
168,3
168,3
219,1
1100
1200
1300
15
15
15
20
20
20
96400
96400
96400
15,7
15,7
15,7
78600
78600
78600
11,7
11,7
11,7
Flooded multi-pipe type
164
174
180
1000
1000
1000
(as required)
Victaulic
®
type
8
6
6
6
168,3
168,3
168,3
Colour code RAL 7035
1400
1500
15
15
20
22
96400
106040
15,7
15,7
78600
86460
11,7
11,7
189
189
1000
1000
6
6
168,3
168,3