Relay Outputs; Analog/Digital Inputs; Digital Outputs - Eaton RI-2 Installation Manual

Relay interface
Table of Contents

Advertisement

Relay Outputs

There are 8 Relay Outputs that can be wired to
provide low voltage or line voltage outputs.
Normally open and Normally closed
terminals available for each relay
Low voltage volt free outputs
Line voltage rated at 3 Amps AC for
general use, resistive, incandescent
lamps (tungsten), electric discharge
(ballast) loads and ¼ HP AC motor loads
for use at 120 and 240 VAC.
Do not mix low voltage and line voltage
on relay output terminals
Controlled as channels 1-8
Connections are made via two 12-way 2 part
connectors with screw terminals.
Wire Gauge for Relay Outputs: Terminals
suitable for wire sizes from 24AWG (0.25mm2)
to 12AWG (4mm2).
The unit is supplied with knockouts, suitable
for 3/4" (19mm) cable glands, for relay output
wiring. An appropriate cable gland should
be fitted to each knockout hole to protect the
cabling from damage.

Analog/Digital Inputs

The unit has eight inputs which can be
configured via software for either digital or
analog input signals.
Individually programmable to be analog or
switch inputs
Analog inputs accept 0 – 10VDC signals
Note: Wire distance from the device to the
RI-2 should not exceed 32 feet (10m).
Connections are made via a 9-way two part
connector with screw terminals.
The unit is supplied with knockouts, suitable
for 3/4" (19mm) cable glands, for analog/digital
input cabling. An appropriate cable gland
should be fitted to the knockout hole to protect
the cabling from damage.
Wire Gauge for inputs: terminals suitable for
wire sizes from 24AWG (0.25mm2) to 12AWG
(4mm2).
Eaton - Lighting Systems

Digital Outputs

The unit has eight digital outputs. These can be
configured as:
LED drive indicators of switched output
status
Digital control channels
Controlled as channels 9-16
Connections are made via the 9-way two part
connector with screw terminals.
Wire Gauge for Digital outputs: terminals
suitable for wire sizes from 24 AWG
(0.25mm2) to 12 AWG (4mm2).
The unit is supplied with knockouts, suitable
for 3/4" (19mm) cable glands, for digital output
wiring. An appropriate cable gland should
be fitted to the knockout hole to protect the
cabling from damage.
iLight Product Series - RI-2
73-897-00
IM8791
Iss 5
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents