4. Wiring for Variable Water Flow Valve

Notes
The variable water flow valve control PCB can control maximum two valves.
Case of one valve, the slave signal connecter must not use.
The power (AC 24V) and signal (DC 0~10V) line is recommended by AWG 23 (0.573mm, 0.0668Ω/m) .
12 Variable Water Flow Control Kit
AC 24V Power
Source for Variable
Water Flow Valve
Slave
Master
DC 0~10V Control
Signal for Variable
Water Flow Valve
Central
Control
Device