Safety information ..................2 Chapter 1 Basics ................1-1 Safety information for Users..............1-2 Overview System 100V ................ 1-3 General Description of the System 100V..........1-4 Assembly dimensions................1-5 Chapter 2 Decentral block periphery PROFIBUS DP ..... 2-1 Principles....................2-2 System overview ..................
Chapter 1: Basics This introduction includes recommendations on the handling of the modules of the VIPA System 100V as central resp. decentral automation system. Besides a system overview you will find general information to the System 100V like dimensions, installation and operating conditions.
Page 6
Manual VIPA System 100V Objective and This manual describes the System 100V decentral block periphery PROFIBUS from VIPA. It contains a description of the construction, project contents implementation and usage. This manual is part of the documentation package with order number...
Manual VIPA System 100V Safety information Safety information The System 100V is constructed and manufactured for Applications conforming with • communication and process control specifications • general control and automation applications • industrial applications • operation within the environmental conditions specified in the technical data •...
Page 8
Safety information Manual VIPA System 100V HB100E - SM-PB - Rev. 13/04...
Basics This introduction includes recommendations on the handling of the Overview modules of the VIPA System 100V as central resp. decentral automation system. Besides a system overview you will find general information to the System 100V like dimensions, installation and operating conditions.
Chapter 1 Basics Manual VIPA System 100V Safety information for Users VIPA modules make use of highly integrated components in MOS- Handling of technology. These components are extremely sensitive to over-voltages electrostatically that can occur during electrostatic discharges. sensitive modules...
Manual VIPA System 100V Chapter 1 Basics Overview System 100V The System 100V from VIPA is a compact central and decentral usable General automation system from VIPA. The system is recommended for lower and middle performance needs. At a System 100V module, CPU res. bus coupler are integrated together with in-/output functions in one case.
• Dimensions basic module: 4tier width: (WxHxD) in mm: 101.6x76x48 / in inches: 4x3x1.9 6tier width: (WxHxD) in mm: 152.4x76x48 / in Inches: 6x3x1.9 The installation of a System 100V module works via snapping on a norm Installation profile head rail.
Manual VIPA System 100V Chapter 1 Basics Assembly dimensions Installation dimensions Installed and 45 mm 44 mm wired dimensions 34 mm 48 mm ca. 70 mm HB100E - SM-PB - Rev. 13/04...
Page 14
Chapter 1 Basics Manual VIPA System 100V CPU 11x with 50 mm 51 mm EasyConn from 45 mm VIPA 11 mm 5 mm 85 mm 8 cm HB100E - SM-PB - Rev. 13/04...
Overview components. The decentral block periphery is available in different variants described in this chapter. This chapter includes all information required for assembly, project engineering and operating this System 100V components. Content Topic Page Chapter 2 Decentral block periphery PROFIBUS DP ..... 2-1 Principles....................
Typical slave equipment holds data of peripheral equipment, sensors, drives, transducers. The VIPA PROFIBUS-couplers of the System 100V are slave devices that transfer data between the System 100V periphery and the leading master. These devices do not have bus access permission in accordance with the PROFIBUS standard.
Page 17
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP The bus communication protocol provides two procedures for accessing Communication the bus: Communications with the master is also referred to as token passing Master to Master procedure. Token passing guarantees that the station receives access permission to the bus.
Page 18
PII: Process image of the inputs PIQ: Process image of the outputs In one V-Bus cycle (i.e. VIPA backplane bus), all input data of the single V-Bus cycle modules are collected in the PII and all output data from the PIQ are transferred to the output modules.
Page 19
To configure the slave connections in your own configuration tool, you’ve GSD-file got all the information about your VIPA modules in form of an electronic data sheet file. Structure and content of this file are dictated by the PROFIBUS User Organization (PNO) and are available there.
In the System 100V, the System 200V technology is integrated in a compact casing. One System 100V unit consists of a PROFIBUS DP coupler and a combina- tion of in-/output channels and expansion clamps. Product overview Old order no.
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Structure Front view [1] LED status monitor [2] PROFIBUS interface [3] Address selector [4] Power supply DC24V [5] Input / output periphery L+ M PE Components LEDs At the frontside there are 3 LEDs for bus diagnostic. The usage and the...
Page 22
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V RS485 interface Via a 9pin RS485 interface you include your PROFIBUS slave into your PROFIBUS. The pin assignment of this interface is shown in this table: Assignment screen n.c.
Page 23
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP The digital input section of a System 100V module collects the binary Input section control signals of the process level and transmits them to the leading PROFIBUS. Every input channel shows its status via a green LED with a time delay of max.
Page 24
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V The digital output section collects the binary control signals of the leading Output section PROFIBUS and transmits them to the process level by means of the outputs. The output section has to be additionally provided with DC 24V via the front-facing connector (see also circuit diagrams).
Page 25
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP The In-/Output section has 4 I/O channels that may be used as input or as In-/Output output channels and 4 normal outputs. Every I/O channel is provided with a section diagnostic function, i.e.
Page 26
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V At the relay output section, you apply the load voltage on the L+ clamp (10 Relay output or 1). From a sum current of 16A on, the load voltage has to be shared between the clamps 1 and 10.
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Assembly and cabling System 100V modules are clipped to 35mm standard norm profile rails. Assembly/ Dismantling For the dismantling you have to pull down the locker with a screwdriver and lift the module from the profile rail.
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Link up to PROFIBUS • The VIPA PROFIBUS DP network must have a linear structure. PROFIBUS in general • PROFIBUS DP consists of minimum one segment with at least one master and one slave.
Page 29
In PROFIBUS all participants are wired parallel. For that purpose, the bus bus connector cable must be feed-through. Via the order number VIPA 972-0DP10 you may order the bus connector "EasyConn". This is a bus connector with switchable terminating resistor and integrated bus diagnostic.
Page 30
A (EN50170). Starting with release 5 you also can use highly flexible bus cable: Lapp Kabel order no.: 2170222, 2170822, 2170322. With the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating tool that makes the connection of the EasyConn much easier.
Note! Please make sure, that you use the same address in your configuration! Project On the included disc you will find the GSD-file of the System 100V in the GSD-folder. Copy it to the GSD-directory of your configuration tool. engineering When using the configuration tool WinNCS from VIPA together with an IM208-Master from VIPA, the GSD-file is part of WinNCS.
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Diagnostic At request from the master or at an error event, the integrated PROFIBUS coupler sends a 13Byte diagnostic telegram. At this time only the digital output units are diagnosable.
Page 33
The Byte 3 of the norm diagnostic data contains the address of the PROFIBUS master that parameterizes the System 100V module. When an FFh is entered here, the according System 100V module is not parameterized in the master. HB100E - SM-PB - Rev. 13/04...
Page 34
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Device related The device related diagnostic data contain detailed information about the periphery of the System 100V. diagnostic data (Byte 6 ... Byte 12) The device related diagnostic data have the following structure: Bit No.
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Technical Data PROFIBUS DP slave with digital input SM 151 151-4PH00 Order no. 151-4PH00 Type SM 151 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V...
Page 37
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 151-4PH00 Max. potential difference between inputs (Ucm) Max. potential difference between Mana and Mintern (Uiso) Max. potential difference between inputs and Mana (Ucm) Max. potential difference between inputs and Mintern (Uiso) Max.
Page 38
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 151-6PH00 Order no. 151-6PH00 Type SM 151 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation)
Page 39
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 151-6PH00 Max. potential difference between Mintern and outputs Insulation tested with DC 500 V Hardware configuration Racks, max. Modules per rack, max. Number of digital modules, max.
Page 40
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 151-6PL00 Order no. 151-6PL00 Type SM 151 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation)
Page 41
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 151-6PL00 Max. potential difference between Mintern and outputs Insulation tested with DC 500 V Hardware configuration Racks, max. Modules per rack, max. Number of digital modules, max.
Page 42
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V SM 152 PROFIBUS DP slave with digital output 152-4PH00 Order no. 152-4PH00 Type SM 152 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V...
Page 43
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 152-4PH00 Between channels of groups to Between channels and backplane bus Between channels and power supply Max. potential difference between circuits Max. potential difference between inputs (Ucm) Max.
Page 44
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 152-6PH00 Order no. 152-6PH00 Type SM 152 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation)
Page 45
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 152-6PH00 Between channels and power supply Max. potential difference between circuits Max. potential difference between inputs (Ucm) Max. potential difference between Mana and Mintern (Uiso) Max. potential difference between inputs and Mana (Ucm) Max.
Page 46
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 152-6PL00 Order no. 152-6PL00 Type SM 152 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation)
Page 47
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 152-6PL00 Between channels and power supply Max. potential difference between circuits Max. potential difference between inputs (Ucm) Max. potential difference between Mana and Mintern (Uiso) Max. potential difference between inputs and Mana (Ucm) Max.
Page 48
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 152-6PH50 Order no. 152-6PH50 Type SM 152 Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection Current consumption (no-load operation)
Page 49
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 152-6PH50 Between channels and power supply Max. potential difference between circuits Max. potential difference between inputs (Ucm) Max. potential difference between Mana and Mintern (Uiso) Max. potential difference between inputs and Mana (Ucm) Max.
Page 50
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V SM 153 PROFIBUS DP Slave with digital in-/output 153-4PF00 Order no. 153-4PF00 Type SM 153, PB-DP slave Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V...
Page 51
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 153-4PF00 Parallel switching of outputs for redundant control not possible of a load Parallel switching of outputs for increased power not possible Actuation of digital input Switching frequency with resistive load max.
Page 52
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Order no. 153-4PF00 Number of TxPDOs, max. Number of RxPDOs, max. Datasizes Input bytes Output bytes Parameter bytes 7 + 5 Diagnostic bytes Housing Material PPE / PA 6.6...
Page 53
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP 153-4PH00 Order no. 153-4PH00 Type SM 153, PB-DP slave Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection...
Page 54
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Parallel switching of outputs for increased power not possible Actuation of digital input Switching frequency with resistive load max. 1000 Hz Switching frequency with inductive load max. 0.5 Hz Switching frequency on lamp load max.
Page 55
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Input bytes Output bytes Parameter bytes 7 + 5 Diagnostic bytes Housing Material PPE / PA 6.6 Mounting Profile rail 35 mm Mechanical data Dimensions (WxHxD) 101.6 x 76 x 48 mm...
Page 56
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 153-6PH00 Order number 153-6PH00 Type SM 153, PB-DP slave Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection...
Page 57
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order number 153-6PH00 Actuation of digital input Switching frequency with resistive load max. 1000 Hz Switching frequency with inductive load max. 0.5 Hz Switching frequency on lamp load max. 10 Hz...
Page 58
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Order number 153-6PH00 Input bytes Output bytes Parameter bytes 7 + 5 Diagnostic bytes Housing Material PPE / PA 6.6 Mounting Profile rail 35 mm Mechanical data Dimensions (WxHxD) 152.4 x 76 x 48 mm...
Page 59
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP 153-6PL00 Order number 153-6PL00 Type SM 153, PB-DP slave Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection...
Page 60
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Order number 153-6PL00 Actuation of digital input Switching frequency with resistive load max. 1000 Hz Switching frequency with inductive load max. 0.5 Hz Switching frequency on lamp load max. 10 Hz...
Page 61
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order number 153-6PL00 Input bytes Output bytes Parameter bytes 7 + 5 Diagnostic bytes Housing Material PPE / PA 6.6 Mounting Profile rail 35 mm Mechanical data Dimensions (WxHxD) 152.4 x 76 x 48 mm...
Page 62
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V 153-6PL10 Order no. 153-6PL10 Type SM 153, PB-DP slave Technical data power supply Power supply (rated value) DC 24 V Power supply (permitted range) DC 20.4...28.8 V Reverse polarity protection...
Page 63
Manual VIPA System 100V Chapter 2 Decentral block periphery PROFIBUS DP Order no. 153-6PL10 Parallel switching of outputs for increased power not possible Actuation of digital input Switching frequency with resistive load max. 1000 Hz Switching frequency with inductive load max.
Page 64
Chapter 2 Decentral block periphery PROFIBUS DP Manual VIPA System 100V Order no. 153-6PL10 Datasizes Input bytes Output bytes Parameter bytes 7 + 5 Diagnostic bytes Housing Material PPE / PA 6.6 Mounting Profile rail 35 mm Mechanical data Dimensions (WxHxD) 152.4 x 76 x 48 mm...