Outdoor Unit - Sanyo W-3WAY ECO-i 85464369098000 Installation Instructions Manual

W-3way eco-i system air conditioner
Table of Contents

Advertisement

2-2. Outdoor Unit

AVOID:
● heat sources, exhaust fans, etc.
● damp, humid or uneven locations
● indoors (no-ventilation location)
DO:
● choose a place as cool as possible.
● choose a place that is well ventilated.
● allow enough room around the unit for air intake/
exhaust and possible maintenance.
Installation Space
Install the outdoor unit where there is enough space for ven-
tilation. Otherwise the unit may not operate properly. Fig. 2-6
shows the minimum space requirement around the outdoor
units when 3 sides are open and only 1 side is shuttered,
with open space above the unit. The mounting base should
be concrete or a similar material that allows for adequate
drainage. Make provisions for anchor bolts, platform height,
and other site-specific installation requirements.
CAUTION
NOTE
● Do not do any wiring or tubing within 1 ft. of the front
panel, because this space is needed as a servicing
space for the compressor.
● Ensure a base height of 4 in. or more to ensure that
drainage water does not accumulate and freeze
around the bottom of the unit.
● If installing a drain pan, install the drain pan prior to
installing the outdoor unit.
* Make sure there is at least 6 in. between the outdoor
unit and the ground.
Also, the direction of the tubing and electrical wiring
should be from the front of the outdoor unit.
W-3WAY_ECO-i_US.indd 24
W-3WAY_ECO-i_US.indd 24
● Leave space open above the
unit.
● Construct louvers or other
openings in the wall, if nec-
essary, to ensure adequate
ventilation.
Hot air
Out-
door
unit
Fig. 2-5
Example of installation of 2 units
(When wall height is below 6 ft.)
* More than 4 in.
More than
2 in.
* More than 4 in.
* However, be sure to ensure a space of 1 ft. or more at
either the right side or the rear of the unit.
Fig. 2-6
74-1/64 (Ceiling panel dimensions)
35-3/64 (Ceiling panel dimensions)
35-3/64 (Ceiling panel dimensions)
31-7/64 (Installation hole pitch)
31-7/64 (Installation hole pitch)
70-5/64 (Installation hole pitch)
Top view
Fig. 2-7
24
Exhaust fan
Heat
source
* More than 4 in.
More than
1.7 ft.
3-15/16
7-7/8
Unit: in.
2008/02/07 10:55:43
2008/02/07 10:55:43