Preparation For Suspending; Placing The Unit Inside The Ceiling - Sanyo W-3WAY ECO-i 85464369098000 Installation Instructions Manual

W-3way eco-i system air conditioner
Table of Contents

Advertisement

■ 4-Way Air Discharge Semi-Concealed Type (XM
Type)

3-8. Preparation for Suspending

This unit uses a drain pump. Use a carpenter's level to check
that the unit is level.
3-9. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching
them to the ceiling support structure, or by any other
method that ensures that the unit will be securely
and safely suspended. (Fig. 3-29)
(2) Follow the diagram to make the holes in the ceiling.
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The dia-
gram shows the relationship between the positions
of the suspension fitting, unit, and panel. (Fig. 3-30)

3-10. Placing the Unit Inside the Ceiling

(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 3-31)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
(2) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" as shown in
the diagram. (Fig. 3-31)
(3) Thread the 3 hexagonal nuts and 2 washers (field
supply) onto each of the 4 suspension bolts as
shown in the diagram. Use 1 nut and 1 washer for
the upper side, and 2 nuts and 1 washer for the
lower side, so that the unit will not fall off the suspen-
sion lugs. (Fig. 3-32)
(4) Adjust so that the distance between the unit and the
ceiling bottom is 33/64" to 45/64". Tighten the nuts
on the upper side and lower side of the suspension
lug. (Fig. 3-32)
(5) Remove the protective polyethylene used to protect
the fan parts during transport.
W-3WAY_ECO-i_US.indd 35
W-3WAY_ECO-i_US.indd 35
Hole-in-anchor
Hole-in-plug
Suspension bolt (M10 or 3/8")
(field supply)
23-5/8"
Ceiling opening dimensions
21-1/32" Suspension bolt pitch
22-41/64"
2-3/32"
6-19/64"
Power supply port
Refrigerant tubing joint
(liquid side)
ø1/4 (flared)
Full-scale installation diagram
Supplied bolt
(printed on top of container box)
Nuts and washers
(used for upper and lower)
Double nut
35
Concrete
Insert
Fig. 3-29
Drain tube
connection port
6-11/16"
(outer dia ø1-1/32")
Fig. 3-30
Fig. 3-31
Suspension bolt
Suspension lug
Notch
33/64" – 45/64"
Fig. 3-32
2008/02/07 10:55:51
2008/02/07 10:55:51
XM