CAUTION
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug
(CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of
the outdoor units. (When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no connection wir-
ing between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wir-
ing. Star branch wiring causes mis-address setting. (Fig. 5-2)
Outdoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 5-3)
Branch
point
16 or fewer