■ Concealed Duct High-Static Pressure Type (D Type)

3-25. Required Minimum Space for Installation and
Service
This air conditioner is usually installed above the ceiling
so that the indoor unit and ducts are not visible. Only the
air intake and air outlet ports are visible from below.
The minimum space for installation and service is shown
in Fig. 3-100.
It is recommended that space be provided (23-5/8" ×
23-5/8") for checking and servicing the electrical system.
Fig. 3-101 and Table 3-3 show the detailed dimensions of
the indoor unit.
D
Table 3-5
Length
A
Type
16-17/32
15-35/64
36
17-23/32
16-47/64
48
W-3WAY_ECO-i_US.indd 52
W-3WAY_ECO-i_US.indd 52
7 3-15/16 = 27-9/16
22 - ø1/8
(Hole for full
circumference)
Unit: in.
B
C
2-43/64
3-55/64
1-13/16
16 - ø1/8
(Hole for full
circumference)
19/32
38-37/64 (Suspension bolt pitch)
24-13/32
19-11/16
2-3/4
1-3/8
25/64
25/64
5-1/8
37
38-37/64
Suspension
bolt pitch
Inspection access
(23-5/8" × 23-5/8")
Drain pan
Ceiling face
37
31-7/32
2-5/32
25/32
3-35/64
1-37/64
2-23/64
1-57/64
Electrical component box
4-ø20 hole for
suspension bolt
4 3-15/16
Refrigerant liquid line (ø3/8 or ø1/4)
= 15-3/4
Refrigerant gas line (ø3/4 or ø5/8)
19-11/16
Power supply outlet
Drain connection (25A, O.D. 1-1/4")
19/32
Duct connection for suction
Duct connection for discharge
39-49/64
Inter-unit control wiring
37
1-3/8
Drain pan
Fig. 3-101
52
Min. 23-5/8
19-11/16
(Space for service)
11-27/64
Suspension
bolt pitch
Air suction side
Refrigerant tubing
Electrical
component
Min. 23-5/8
box
Space for
service
Min. 22-53/64
Min. 5-1/8
Unit: in.
Fig. 3-100
Unit: in.
2008/02/07 10:56:00
2008/02/07 10:56:00