Tubing Size; Straight Equivalent Length Of Joints; Additional Refrigerant Charge - Sanyo W-3WAY ECO-i 85464369098000 Installation Instructions Manual

W-3way eco-i system air conditioner
Table of Contents

Advertisement

Table 1-13 Indoor Unit Tubing Connection Size (
Indoor unit type
Total system horsepower
Distribution
Suction tubing
joint –
Discharge tubing
solenoid valve
kit tubing
Liquid tubing
Solenoid valve
Gas tubing
kit – Indoor
unit tubing
connection
Liquid tubing
*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.

1-7. Straight Equivalent Length of Joints

Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 1-14 Straight Equivalent Length of Joints
Gas tubing size (in.(mm))
90 elbow
45 elbow
U-shape tube bent
(R2–23/64–3–15/16 in.)
T r ap bend
Y-branch distr ibution joint
Ball v alve f or ser vice
Table 1-15 Refrigerant tubing (Existing tubing can be used.)
Material O
ø1/4" (ø6.35)
ø3/8" (ø9.52)
ø1/2" (ø12.7)
ø5/8" (ø15.88)
t5/128 (t1.0)
ø3/4" (ø19.05)
over t5/128 (t1.0)
ø7/8" (ø22.22)
t5/128 (t1.0)

1-8. Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
Table 1-16-1 Amount of Refrigerant Charge Per ft.,
According to Liquid Tubing Size
Liquid tubing
ø1/4"
size
(ø6.35)
(ø9.52)
Amount of
refrigerant
0.279 0.602
charge (oz/ft.)
Table 1-16-2 Necessary Amount of Refrigerant
Charge Per Unit
CHDZ09053
CHDZR09053
W-3WAY_ECO-i_US.indd 13
W-3WAY_ECO-i_US.indd 13
7
9
0.8
1
ø1/2"
(ø12.70)
ø1/4"
(ø6.35)
1/2"
5/8"
(12.7)
(15.88)
(19.05)
1 ft.
1.1 ft.
(0.30 m)
(0.35 m)
(0.42 m)
0.8 ft.
0.9 ft.
(0.23 m)
(0.26 m)
(0.32 m)
3 ft.
3.4 ft.
(0.90 m)
(1.05 m)
(1.26 m)
7.5 ft.
9.2 ft.
10.5 ft.
(2.30 m)
(2.80 m)
(3.20 m)
Equivalent length con version not needed.
Equivalent length con version not needed.
Tubing size (in. (mm))
Material 1/2H • H
t1/32 (t0.8)
t1/32 (t0.8)
ø1-1/8" (ø28.58)
t1/32 (t0.8)
ø1-1/4" (ø31.75)
ø1-1/2" (ø38.10)
ø1-5/8" (ø41.28)
ø3/8"
ø1/2"
ø5/8"
ø3/4"
ø7/8"
(ø12.7)
(ø15.88)
(ø19.05)
(ø22.22)
1.38
1.99
2.78
3.93
CHDZ14053
CHDZR14053
113 oz/unit
)
1
40
18
24
12
36
1.3
2
3
4
ø5/8"
(ø15.88)
ø1/2"
(ø12.70)
ø3/8"
(ø9.52)
ø5/8"
(ø15.88)
ø3/8"
(ø9.52)
3/4"
7/8"
1"
1-1/8"
(22.22)
(25.4)
(28.58)
1.4 ft.
1.6 ft.
1.7 ft.
1.9 ft.
(0.48 m)
(0.52 m)
(0.57 m)
1 ft.
1.2 ft.
1.3 ft.
1.4 ft.
(0.36 m)
(0.39 m)
(0.43 m)
4.1 ft.
4.7 ft.
5.1 ft.
5.6 ft.
(1.44 m)
(1.56 m)
(1.71 m)
12.5 ft.
14.1 ft.
15.4 ft.
(3.80 m)
(4.30 m)
(4.70 m)
* When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
t5/128 (t1.0)
crushing or damaging the tubes when
t3/64 (t1.1)
bending them.
over t3/64 (t1.15)
over t3/64 (t1.20)
Required amount of charge = Necessary Amount of
Refrigerant Charge Per Unit (14053 Type) + (Amount
of refrigerant charge per ft. of each size of liquid tube
× its tube length) + (...) + (...)
* Always charge accurately using a scale for weighing.
13
in. (mm)
48
5
1-1/4"
1-1/2"
(31.8)
(38.1)
2.3 ft.
2.6 ft.
(0.70m)
(0.79 m)
1.7 ft.
1.9 ft.
(0.53 m)
(0.59 m)
6.9 ft.
7.8 ft.
(2.10 m)
(2.37 m)
16.4 ft.
14.0 ft.
(5.00 m)
(5.80 m)
2008/02/15 12:29:03
2008/02/15 12:29:03