DAIKIN AIR CONDITIONER
Read the precautions in this manual
carefully before operating the unit.
• The precautions described herein are classified as WARNING and CAUTION. They both contain important information
regarding safety. Be sure to observe all precautions without fail.
• Meaning of WARNING and CAUTION notices
WARNING
Failure to follow these instructions properly may result in personal injury or loss of life.
CAUTION
Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.
• The safety marks shown in this manual have the following meanings:
Be sure to follow the instructions.
• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate
the air conditioner and take care of it with the aid of the operation manual.
WARNING
• Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
• Install the air conditioner in accordance with the instructions in this installation manual.
• Be sure to use only the specified accessories and parts for installation work.
• Install the air conditioner on a foundation strong enough to hold the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injury.
• Electrical work must be performed in accordance with relevant local and national regulations and with the instructions in this installation manual.
Be sure to use a dedicated power supply circuit only.
• Use a cable of suitable length.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal
connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the
control box lid can be securely fastened.
• If refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
• After completing installation, check for refrigerant gas leakage.
leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
• When installing or relocating the air conditioner, do not let any other substances besides R32, such as air, enter the refrigerant circuit.
The presence of air or other foreign matter in the refrigerant circuit causes an abnormal pressure rise, which may result in equipment damage and even injury.
• During installation, attach the refrigerant piping securely before operating the compressor.
open when the compressor is operated, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• During pump down, stop the compressor before removing the refrigerant piping.
air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
• Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.
• Be sure to install an earth leakage circuit breaker.
• Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
• The appliance must be stored in a room without continuously operating ignition sources (for example: open flames,
an operating gas appliance or an operating electric heater).
• Do not pierce or burn.
• Be aware that refrigerants may not contain an odour.
• The appliance must be installed, operated and stored in a room with a floor area larger than 4.9m
• Comply with national gas regulations.
Safety Precautions ( 1 )
Be sure to establish an earth connection.
Insufficient power supply and improper workmanship may result in electric shocks or fire.
Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.
Improper positioning of the control box lid may result in electric shocks, fire or overheating terminals.
Failure to install an earth leakage circuit breaker may result in electric shocks or fire.
3P384095-1A M14B148A
This appliance is filled with R32.
Improper installation may result in water leakage, electric shocks or fire.
Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
Toxic gas may be produced if the refrigerant gas
If the refrigerant pipes are not attached and the stop valve is
If the compressor is still operating and the stop valve is open during pump down,
The two-dimensional bar code
is a manufacturing code.
Never attempt.
.
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3P384095-1A and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin 3P384095-1A

  • Page 1 3P384095-1A M14B148A DAIKIN AIR CONDITIONER The two-dimensional bar code is a manufacturing code. Safety Precautions ( 1 ) Read the precautions in this manual This appliance is filled with R32. carefully before operating the unit. • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety.
  • Page 2: Safety Precautions ( 2 )

    If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. • Only qualified personnel can handle, fill, purge and dispose of the refrigerant. N004  This product is not designed for re-packing. In case of re-packing contact to Daikin dealer. Accessories Mounting plate fixing...
  • Page 3: Indoor Unit Installation Drawings

    Indoor Unit Installation Drawings How to attach the indoor unit. Hook the tabs of the bottom frame A Mounting plate to the mounting plate. The mounting plate If the tabs are difficult to hook, should be installed on a remove the front grille. wall which can support the weight of the indoor unit.
  • Page 4: Indoor Unit Installation

    Indoor Unit Installation (1) Installing the mounting plate • The mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall.
  • Page 5 Indoor Unit Installation (2) 3-2. Left-side, left-back, or left-bottom piping Remove pipe port cover here for 1) Attach the drain hose to the underside of the refrigerant left-side piping. pipes with adhesive vinyl tape. Left-side piping 2) Be sure to connect the drain hose to the drain port in Remove pipe port cover here for left-bottom piping.
  • Page 6: Refrigerant Piping Work

    Indoor Unit Installation (3) When connecting to an HA system Pull Pull 1) Remove the front grille. HA connector (S21) (6 screws) Slide 2) Remove the electrical wiring box. (1 screw) Metal plate electrical cover 3) Remove the metal plate Slide Lay the HA cord as electrical wiring box cover.
  • Page 7: Selection Of Copper And Heat Insulation Materials

    Refrigerant Piping Work (2) Refrigerant piping CAUTION • Use the flare nut fixed to the main unit. (This is to prevent cracking of the flare nut as a result of deterioration over time.) • To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32.) •...
  • Page 8: Trial Operation And Testing

    Trial Operation and Testing Trial operation and testing • Trial operation should be carried out in either COOL or HEAT operation. 1-1 Measure the supply voltage and make sure that it is within the specified range. 1-2 In COOL operation, select the lowest programmable temperature; in HEAT operation, select the highest programmable temperature.
  • Page 9 3P384095-1A M14B148A ‫ﻣﻜﻴﻒ اﻟﻬﻮاء ﻣﻦ داﻳﻜﻦ‬ ‫دﻟﻴﻞ اﻟﺘﺮﻛﻴﺐ‬ (1) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫اﻗﺮأ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﳌﻮﺟﻮدة ﻓﻲ ﻫﺬا‬ . R32 ‫ﲤﺖ ﺗﻌﺒﺌﺔ ﻫﺬا اﳉﻬﺎز ﺑﻐﺎز‬ .‫اﻟﺪﻟﻴﻞ ﺑﻌﻨﺎﻳﺔ ﻗﺒﻞ ﺗﺸﻐﻴﻞ اﻟﻮﺣﺪة‬ ‫ﰎ ﺗﺼﻨﻴﻒ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﻟﻮاردة ﻫﻨﺎ إﻟﻰ ﻧﻮﻋﲔ وﻫﻤﺎ ﲢﺬﻳﺮ و ﺗﻨﺒﻴﻪ. ﻳﺤﺘﻮي ﻛﻼﻫﻤﺎ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎت ﻫﺎﻣﺔ ﺗﺘﻌﻠﻖ ﺑﺎﻟﺴﻼﻣﺔ. اﺣﺮص ﻋﻠﻰ اﺗﺒﺎع ﺟﻤﻴﻊ‬...
  • Page 10 (2) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫ﺗﻨﺒﻴﻪ‬ .‫ﻻ ﺗﻌﻤﺪ إﻟﻰ ﺗﺮﻛﻴﺐ ﻣﻜﻴﻒ اﻟﻬﻮاء ﻓﻲ أي ﻣﻜﺎن ﳝﻜﻦ أن ﻳﺆدي إﻟﻰ ﺧﻄﺮ ﺗﺴﺮب اﻟﻐﺎزات اﻟﻘﺎﺑﻠﺔ ﻟﻼﺷﺘﻌﺎل‬ • .‫ﻓﻲ ﺣﺎل ﺣﺪوث ﺗﺴﺮب ﻟﻠﻐﺎز، ﻗﺪ ﻳﺆدي ﺗﺮاﻛﻢ اﻟﻐﺎز ﺑﺎﻟﻘﺮب ﻣﻦ ﻣﻜﻴﻒ اﻟﻬﻮاء إﻟﻰ اﻧﺪﻻع ﺣﺮﻳﻖ‬ .‫ﺑﻴﻨﻤﺎ...
  • Page 11 ‫ﻣﺨﻄﻄﺎت ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ .‫ﻛﻴﻔﻴﺔ ﺗﺜﺒﻴﺖ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ ‫ﻗﻢ ﺑﺮﺑﻂ اﻷﻟﺴﻨﺔ اﳋﺎﺻﺔ ﺑﺎﻹﻃﺎر اﻟﺴﻔﻠﻲ‬ ‫إﻟﻰ أن ﺗﺼﻞ إﻟﻰ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ ‫إذا ﻛﺎن ﻣﻦ اﻟﺼﻌﺐ رﺑﻂ اﻷﻟﺴﻨﺔ، اﻧﺰع‬ ‫ﻳﻨﺒﻐﻲ ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ ﻋﻠﻰ‬ ‫اﻟﻠﺴﺎن‬ .‫اﻟﺸﺒﻜﺔ اﻷﻣﺎﻣﻴﺔ‬ ‫ﺟﺪار ﺑﺤﻴﺚ ﺗﺘﻤﻜﻦ ﻣﻦ ﲢﻤ ﹼ ﻞ وزن‬ .‫اﻟﻮﺣﺪة...
  • Page 12 (1) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ .‫• ﻳﻨﺒﻐﻲ ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ ﻋﻠﻰ ﺟﺪار ﺑﺤﻴﺚ ﺗﺘﻤﻜﻦ ﻣﻦ ﲢﻤ ﹼ ﻞ وزن اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫1( ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ ﻋﻠﻰ اﳉﺪار ﺑﺸﻜ ﻞ ﹴ ﻣﺆﻗﺖ، ﺗﺄﻛﺪ ﻣﻦ وﺿﻊ اﻟﻠﻮﺣﺔ ﺑﻄﺮﻳﻘﺔ ﻣﺴﺘﻮﻳﺔ ﺑﺸﻜ ﻞ ﹴ ﻛﺎﻣﻞ، وﻗﻢ ﺑﻮﺿﻊ ﻋﻼﻣﺔ‬ .‫ﻋﻠﻰ...
  • Page 13 (2) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫3-2 . ﲤﺪﻳﺪ اﻷﻧﺒﻮب اﳉﺎﻧﺒﻲ اﻷﻳﺴﺮ أو اﳋﻠﻔﻲ اﻷﻳﺴﺮ أو اﻟﺴﻔﻠﻲ اﻷﻳﺴﺮ‬ ‫اﻧﺰع ﻏﻄﺎء ﻣﻨﻔﺬ‬ ‫اﻷﻧﺒﻮب ﻟﺘﻤﺪﻳﺪ اﻷﻧﺒﻮب‬ ‫1( ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﺧﺮﻃﻮم اﻟﺘﺼﺮﻳﻒ ﻓﻲ اﳉﺎﻧﺐ اﻟﺴﻔﻠﻲ ﻣﻦ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ‬ .‫اﳉﺎﻧﺒﻲ اﻷﻳﺴﺮ ﻫﻨﺎ‬ ‫ﲤﺪﻳﺪ اﻷﻧﺒﻮب‬ .‫اﻟﺘﺒﺮﻳﺪ ﺑﺸﺮﻳﻂ ﻓﻴﻨﻴﻞ ﻻﺻﻖ‬ ‫اﳉﺎﻧﺒﻲ...
  • Page 14 (3) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ HA ‫ﻋﻨﺪ ﺗﻮﺻﻴﻠﻪ ﺑﻨﻈﺎم‬ ‫اﻟﻠﺴﺎن‬ ‫اﺳﺤﺐ‬ ‫اﺳﺤﺐ‬ (‫1( اﻧﺰع اﻟﺸﺒﻜﺔ اﻷﻣﺎﻣﻴﺔ. ) 6 ﺑﺮاﻏﻲ‬ ‫اﳌﻮﺻﻞ‬ (S21) HA ‫2( اﻧﺰع ﺻﻨﺪوق ﲤﺪﻳﺪ اﻷﺳﻼك‬ ‫ﻗﻢ ﺑﺰﻟﻘﻪ‬ ‫اﻟﻠﺴﺎن‬ (‫اﻟﻜﻬﺮﺑﺎﺋﻴﺔ. ) 1 ﺑﺮﻏﻲ‬ ‫3( اﻧﺰع اﻟﻠﻮﺣﺔ اﳌﻌﺪﻧﻴﺔ ﻣﻦ ﻏﻄﺎء‬ ‫ﻏﻄﺎء اﻟﻠﻮح اﳌﻌﺪﻧﻲ‬ ‫اﻟﻜﻬﺮﺑﺎﺋﻲ‬...
  • Page 15 (2) ‫أﻋﻤﺎل ﲤﺪﻳﺪ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ‬ ‫ﲤﺪﻳﺪ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ‬ ‫ﺗﻨﺒﻴﻪ‬ .‫• اﺳﺘﻌﻤﻞ ﺻﺎﻣﻮﻟﺔ اﻟﺘﻮﺳﻌﺔ اﳌﺜﺒﺘﺔ ﺑﺎﻟﻮﺣﺪة اﻟﺮﺋﻴﺴﻴﺔ‬ (.‫)ﻳ ﹸ ﻌﺪ ﻫﺬا ﻣﻬﻤ ﹰ ﺎ ﻟﺘﻔﺎدي ﺣﺪوث ﺗﺸﻘﻖ ﻓﻲ ﺻﺎﻣﻮﻟﺔ اﻟﺘﻮﺳﻌﺔ ﻛﻨﺘﻴﺠﺔ ﻟﺘﺪﻫﻮر اﻷداء ﻣﻊ ﻣﺮور اﻟﻮﻗﺖ‬ .‫• ﻟﺘﻔﺎدي ﺗﺴﺮﻳﺐ اﻟﻐﺎز، ﻗﻢ ﺑﻮﺿﻊ زﻳﺖ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ ﻋﻠﻰ اﻟﺴﻄﺢ اﻟﺪاﺧﻠﻲ ﻓﻘﻂ ﻣﻦ ﺟﺰء اﻟﺘﻮﺳﻌﺔ‬ (.
  • Page 16 ‫اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ واﻻﺧﺘﺒﺎر‬ ‫اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ واﻻﺧﺘﺒﺎر‬ .‫ﻳﻨﺒﻐﻲ أن ﻳﺘﻢ اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ ﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺒﺮﻳﺪ أو اﻟﺘﺪﻓﺌﺔ‬ • .‫1-1 ﻗﻢ ﺑﻘﻴﺎس اﻹﻣﺪاد ﺑﺎﻟﻔﻮﻟﻄﻴﺔ وﺗﺄﻛﺪ ﻣﻦ أﻧﻬﺎ ﺿﻤﻦ اﻟﻨﻄﺎق اﶈﺪد‬ ،‫1-2 ﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺒﺮﻳﺪ، ﻗﻢ ﺑﺎﺧﺘﻴﺎر أﻗﻞ درﺟﺔ ﺣﺮارة ﻗﺎﺑﻠﺔ ﻟﻠﺒﺮﻣﺠﺔ؛ وﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺪﻓﺌﺔ‬ .‫ﻗﻢ...
  • Page 17: Safety Precautions ( 1 )

    3P384095-2A M14B149A DAIKIN AIR CONDITIONER The two-dimensional bar code is a manufacturing code. Safety Precautions ( 1 ) Read the precautions in this manual This appliance is filled with R32. carefully before operating the unit. • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety.
  • Page 18 If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. • Only qualified personnel can handle, fill, purge and dispose of the refrigerant. N004  This product is not designed for re-packing. In case of re-packing contact to Daikin dealer. Accessories Mounting plate fixing...
  • Page 19 Indoor Unit Installation Drawings How to attach the indoor unit. A Mounting Hook the tabs of the bottom frame plate to the mounting plate. If the tabs are difficult to hook, remove the front grille. How to remove the indoor unit. Bottom frame Push up the marked area (at the A Mounting plate...
  • Page 20: Indoor Unit Installation

    Indoor Unit Installation (1) Installing the mounting plate • The mounting plate should be installed on a wall which can support the weight of the indoor unit. 1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall.
  • Page 21 Indoor Unit Installation (2) 3-2. Left-side, left-back, or left-bottom piping Remove pipe port cover here for 1) Attach the drain hose to the underside of the refrigerant left-side piping. pipes with adhesive vinyl tape. Left-side piping 2) Be sure to connect the drain hose to the drain port in Remove pipe port cover here for left-bottom piping.
  • Page 22: Flaring The Pipe End

    Indoor Unit Installation (3) When connecting to an HA system HA connector (S21) 1) Remove the front grille. Pull Pull (6 screws, 3 front grille fixtures) Slide 2) Remove the electrical Lay the HA cord as shown in the figure. wiring box.
  • Page 23: Selection Of Copper And Heat Insulation Materials

    Refrigerant Piping Work (2) Refrigerant piping CAUTION • Use the flare nut fixed to the main unit. (This is to prevent cracking of the flare nut as a result of deterioration over time.) • To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32.) •...
  • Page 24: Trial Operation And Testing

    Trial Operation and Testing Trial operation and testing • Trial operation should be carried out in either COOL or HEAT operation. 1-1 Measure the supply voltage and make sure that it is within the specified range. 1-2 In COOL operation, select the lowest programmable temperature; in HEAT operation, select the highest programmable temperature.
  • Page 25 3P384095-2A M14B149A ‫ﻣﻜﻴﻒ اﻟﻬﻮاء ﻣﻦ داﻳﻜﻦ‬ ‫دﻟﻴﻞ اﻟﺘﺮﻛﻴﺐ‬ (1) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫اﻗﺮأ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﳌﻮﺟﻮدة ﻓﻲ ﻫﺬا‬ . R32 ‫ﲤﺖ ﺗﻌﺒﺌﺔ ﻫﺬا اﳉﻬﺎز ﺑﻐﺎز‬ .‫اﻟﺪﻟﻴﻞ ﺑﻌﻨﺎﻳﺔ ﻗﺒﻞ ﺗﺸﻐﻴﻞ اﻟﻮﺣﺪة‬ ‫ﰎ ﺗﺼﻨﻴﻒ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﻟﻮاردة ﻫﻨﺎ إﻟﻰ ﻧﻮﻋﲔ وﻫﻤﺎ ﲢﺬﻳﺮ و ﺗﻨﺒﻴﻪ. ﻳﺤﺘﻮي ﻛﻼﻫﻤﺎ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎت ﻫﺎﻣﺔ ﺗﺘﻌﻠﻖ ﺑﺎﻟﺴﻼﻣﺔ. اﺣﺮص ﻋﻠﻰ اﺗﺒﺎع ﺟﻤﻴﻊ‬ •...
  • Page 26 (2) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫ﺗﻨﺒﻴﻪ‬ .‫ﻻ ﺗﻌﻤﺪ إﻟﻰ ﺗﺮﻛﻴﺐ ﻣﻜﻴﻒ اﻟﻬﻮاء ﻓﻲ أي ﻣﻜﺎن ﳝﻜﻦ أن ﻳﺆدي إﻟﻰ ﺧﻄﺮ ﺗﺴﺮب اﻟﻐﺎزات اﻟﻘﺎﺑﻠﺔ ﻟﻼﺷﺘﻌﺎل‬ • .‫ﻓﻲ ﺣﺎل ﺣﺪوث ﺗﺴﺮب ﻟﻠﻐﺎز، ﻗﺪ ﻳﺆدي ﺗﺮاﻛﻢ اﻟﻐﺎز ﺑﺎﻟﻘﺮب ﻣﻦ ﻣﻜﻴﻒ اﻟﻬﻮاء إﻟﻰ اﻧﺪﻻع ﺣﺮﻳﻖ‬ .‫ﺑﻴﻨﻤﺎ...
  • Page 27 ‫ﻣﺨﻄﻄﺎت ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ .‫ﻛﻴﻔﻴﺔ ﺗﺜﺒﻴﺖ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ ‫ﻗﻢ ﺑﺮﺑﻂ اﻷﻟﺴﻨﺔ اﳋﺎﺻﺔ ﺑﺎﻹﻃﺎر اﻟﺴﻔﻠﻲ‬ ‫إﻟﻰ أن ﺗﺼﻞ إﻟﻰ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ ‫إذا ﻛﺎن ﻣﻦ اﻟﺼﻌﺐ رﺑﻂ اﻷﻟﺴﻨﺔ، اﻧﺰع‬ ‫اﻟﻠﺴﺎن‬ .‫اﻟﺸﺒﻜﺔ اﻷﻣﺎﻣﻴﺔ‬ .‫ﻛﻴﻔﻴﺔ ﻧﺰع اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫اﻹﻃﺎر اﻟﺴﻔﻠﻲ‬ ‫ادﻓﻊ اﳌﻨﻄﻘﺔ اﻟﺘﻲ ﲢﻤﻞ ﻋﻼﻣﺔ ﻟﻸﻋﻠﻰ‬ ‫ﻟﻮﺣﺔ...
  • Page 28 (1) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ‬ .‫• ﻳﻨﺒﻐﻲ ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ ﻋﻠﻰ ﺟﺪار ﺑﺤﻴﺚ ﺗﺘﻤﻜﻦ ﻣﻦ ﲢﻤ ﹼ ﻞ وزن اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫1( ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﻟﻮﺣﺔ اﻟﺘﻌﻠﻴﻖ ﻋﻠﻰ اﳉﺪار ﺑﺸﻜ ﻞ ﹴ ﻣﺆﻗﺖ، ﺗﺄﻛﺪ ﻣﻦ وﺿﻊ اﻟﻠﻮﺣﺔ ﺑﻄﺮﻳﻘﺔ ﻣﺴﺘﻮﻳﺔ ﺑﺸﻜ ﻞ ﹴ ﻛﺎﻣﻞ، وﻗﻢ ﺑﻮﺿﻊ ﻋﻼﻣﺔ‬ .‫ﻋﻠﻰ...
  • Page 29 (2) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ ‫3-2 . ﲤﺪﻳﺪ اﻷﻧﺒﻮب اﳉﺎﻧﺒﻲ اﻷﻳﺴﺮ أو اﳋﻠﻔﻲ اﻷﻳﺴﺮ أو اﻟﺴﻔﻠﻲ اﻷﻳﺴﺮ‬ ‫اﻧﺰع ﻏﻄﺎء ﻣﻨﻔﺬ‬ ‫اﻷﻧﺒﻮب ﻟﺘﻤﺪﻳﺪ اﻷﻧﺒﻮب‬ ‫1( ﻗﻢ ﺑﺘﺜﺒﻴﺖ ﺧﺮﻃﻮم اﻟﺘﺼﺮﻳﻒ ﻓﻲ اﳉﺎﻧﺐ اﻟﺴﻔﻠﻲ ﻣﻦ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ‬ .‫اﳉﺎﻧﺒﻲ اﻷﻳﺴﺮ ﻫﻨﺎ‬ .‫اﻟﺘﺒﺮﻳﺪ ﺑﺸﺮﻳﻂ ﻓﻴﻨﻴﻞ ﻻﺻﻖ‬ ‫ﲤﺪﻳﺪ...
  • Page 30 (3) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﻟﺪاﺧﻠﻴﺔ‬ HA ‫ﻋﻨﺪ ﺗﻮﺻﻴﻠﻪ ﺑﻨﻈﺎم‬ ‫اﳌﻮﺻﻞ‬ (S21) HA ‫اﻟﻠﺴﺎن‬ .‫1( اﻧﺰع اﻟﺸﺒﻜﺔ اﻷﻣﺎﻣﻴﺔ‬ ‫اﺳﺤﺐ‬ ‫اﺳﺤﺐ‬ ‫) 6 ﺑﺮاﻏﻲ، 3 ﻣﺜﺒﺘﺎت ﻟﻠﺸﺒﻜﺔ‬ (‫اﻷﻣﺎﻣﻴﺔ‬ ‫ﻗﻢ ﺑﺰﻟﻘﻪ‬ ‫اﻟﻠﺴﺎن‬ ‫2( اﻧﺰع ﺻﻨﺪوق ﲤﺪﻳﺪ اﻷﺳﻼك‬ ‫ﻗﻢ ﺑﺘﻤﺪﻳﺪ اﻟﺴﻠﻚ‬ (‫اﻟﻜﻬﺮﺑﺎﺋﻴﺔ. ) 1 ﺑﺮﻏﻲ‬ .‫ﻛﻤﺎ...
  • Page 31 (2) ‫أﻋﻤﺎل ﲤﺪﻳﺪ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ‬ ‫ﲤﺪﻳﺪ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ‬ ‫ﺗﻨﺒﻴﻪ‬ .‫• اﺳﺘﻌﻤﻞ ﺻﺎﻣﻮﻟﺔ اﻟﺘﻮﺳﻌﺔ اﳌﺜﺒﺘﺔ ﺑﺎﻟﻮﺣﺪة اﻟﺮﺋﻴﺴﻴﺔ‬ (.‫)ﻳ ﹸ ﻌﺪ ﻫﺬا ﻣﻬﻤ ﹰ ﺎ ﻟﺘﻔﺎدي ﺣﺪوث ﺗﺸﻘﻖ ﻓﻲ ﺻﺎﻣﻮﻟﺔ اﻟﺘﻮﺳﻌﺔ ﻛﻨﺘﻴﺠﺔ ﻟﺘﺪﻫﻮر اﻷداء ﻣﻊ ﻣﺮور اﻟﻮﻗﺖ‬ .‫• ﻟﺘﻔﺎدي ﺗﺴﺮﻳﺐ اﻟﻐﺎز، ﻗﻢ ﺑﻮﺿﻊ زﻳﺖ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ ﻋﻠﻰ اﻟﺴﻄﺢ اﻟﺪاﺧﻠﻲ ﻓﻘﻂ ﻣﻦ ﺟﺰء اﻟﺘﻮﺳﻌﺔ‬ (.
  • Page 32 ‫اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ واﻻﺧﺘﺒﺎر‬ ‫اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ واﻻﺧﺘﺒﺎر‬ .‫ﻳﻨﺒﻐﻲ أن ﻳﺘﻢ اﻟﺘﺸﻐﻴﻞ اﻟﺘﺠﺮﻳﺒﻲ ﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺒﺮﻳﺪ أو اﻟﺘﺪﻓﺌﺔ‬ • .‫1-1 ﻗﻢ ﺑﻘﻴﺎس اﻹﻣﺪاد ﺑﺎﻟﻔﻮﻟﻄﻴﺔ وﺗﺄﻛﺪ ﻣﻦ أﻧﻬﺎ ﺿﻤﻦ اﻟﻨﻄﺎق اﶈﺪد‬ ،‫1-2 ﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺒﺮﻳﺪ، ﻗﻢ ﺑﺎﺧﺘﻴﺎر أﻗﻞ درﺟﺔ ﺣﺮارة ﻗﺎﺑﻠﺔ ﻟﻠﺒﺮﻣﺠﺔ؛ وﻋﻨﺪ اﻟﺘﺸﻐﻴﻞ ﻓﻲ اﻟﻮﺿﻊ اﻟﺘﺪﻓﺌﺔ‬ .‫ﻗﻢ...
  • Page 33: Safety Precautions

    3P384095-3A M14B150A DAIKIN AIR CONDITIONER Two-dimensional bar code is a manufacturing code. Safety Precautions (1) Read the precautions in this manual This appliance is filled with R32. carefully before operating the unit. • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety.
  • Page 34: Precautions For Selecting The Location

    • The temperature of refrigerant circuit will be high, please keep the inter-unit wires away from copper pipes that are not thermally insulated. • Only qualified personnel can handle, fill, purge and dispose of the refrigerant. N004  This product is not designed for re-packing. In case of re-packing contact to Daikin dealer. Accessories Accessories supplied with the outdoor unit:...
  • Page 35: Precautions On Installation

    Precautions on Installation • Check the strength and level of the installation surface so that the unit does not cause any operating vibration or noise after installation. • In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers;...
  • Page 36: Outdoor Unit Installation

    Outdoor Unit Installation (1) Installing the outdoor unit 1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Drawings”. 2) If drain work is necessary, follow the procedures below. Drain work 1) Use the drain socket for drainage.
  • Page 37 Outdoor Unit Installation (2) Evacuating the air with a vacuum pump and checking for gas leakage WARNING • Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle. • If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible. •...
  • Page 38 Outdoor Unit Installation (3) Refrigerant piping work Wall Be sure to 6-1 Cautions on pipe handling place a cap. Rain If no flare cap is 1) Protect the open end of the pipe against dust and moisture. available, cover the flare mouth with 2) All pipe bends should be as gentle as possible.
  • Page 39 Wiring (2)  How to attach the partition plate. 1) Insert the protrusion of the partition Screws plate into the notch in the metal sheet. 2) Slide the partition plate so that the tab Service lid on the metal sheet fits into the slit on the partition plate.
  • Page 40: Pump Down Operation

    Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve caps from the liquid stop valve and gas stop valve. Hexagonal 2) Carry out forced cooling operation. wrench 3) After 3 to 4 minutes, close the liquid stop valve with a hexagonal wrench.
  • Page 41 3P384095-3A M14B150A ‫ﻣﻜﻴﻒ اﻟﻬﻮاء ﻣﻦ داﻳﻜﻦ‬ ‫دﻟﻴﻞ اﻟﺘﺮﻛﻴﺐ‬ (1) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫اﻗﺮأ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﳌﻮﺟﻮدة ﻓﻲ ﻫﺬا‬ . R32 ‫ﲤﺖ ﺗﻌﺒﺌﺔ ﻫﺬا اﳉﻬﺎز ﺑﻐﺎز‬ .‫اﻟﺪﻟﻴﻞ ﺑﻌﻨﺎﻳﺔ ﻗﺒﻞ ﺗﺸﻐﻴﻞ اﻟﻮﺣﺪة‬ ‫ﰎ ﺗﺼﻨﻴﻒ اﻟﺘﻨﺒﻴﻬﺎت اﻻﺣﺘﻴﺎﻃﻴﺔ اﻟﻮاردة ﻫﻨﺎ إﻟﻰ ﻧﻮﻋﲔ وﻫﻤﺎ ﲢﺬﻳﺮ و ﺗﻨﺒﻴﻪ. ﻳﺤﺘﻮي ﻛﻼﻫﻤﺎ ﻋﻠﻰ ﻣﻌﻠﻮﻣﺎت ﻫﺎﻣﺔ ﺗﺘﻌﻠﻖ ﺑﺎﻟﺴﻼﻣﺔ. اﺣﺮص ﻋﻠﻰ اﺗﺒﺎع ﺟﻤﻴﻊ‬ •...
  • Page 42 (2) ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺴﻼﻣﺔ‬ ‫ﺗﻨﺒﻴﻪ‬ .‫ﻻ ﺗﻌﻤﺪ إﻟﻰ ﺗﺮﻛﻴﺐ ﻣﻜﻴﻒ اﻟﻬﻮاء ﻓﻲ أي ﻣﻜﺎن ﳝﻜﻦ أن ﻳﺆدي إﻟﻰ ﺧﻄﺮ ﺗﺴﺮب اﻟﻐﺎزات اﻟﻘﺎﺑﻠﺔ ﻟﻼﺷﺘﻌﺎل‬ • .‫ﻓﻲ ﺣﺎل ﺣﺪوث ﺗﺴﺮب ﻟﻠﻐﺎز، ﻗﺪ ﻳﺆدي ﺗﺮاﻛﻢ اﻟﻐﺎز ﺑﺎﻟﻘﺮب ﻣﻦ ﻣﻜﻴﻒ اﻟﻬﻮاء إﻟﻰ اﻧﺪﻻع ﺣﺮﻳﻖ‬ .‫ﺑﻴﻨﻤﺎ...
  • Page 43 ‫ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﻟﺘﺮﻛﻴﺐ‬ ‫• ﲢﻘﻖ ﻣﻦ ﻗﻮة ﺳﻄﺢ اﻟﺘﺮﻛﻴﺐ وﻣﺪى اﺳﺘﻮاﺋﻪ ﺑﺤﻴﺚ ﻻ ﺗﺘﺴﺒﺐ اﻟﻮﺣﺪة ﺑﺈﺻﺪار اﻫﺘﺰاز ﻧﺎﰋ ﻋﻦ اﻟﺘﺸﻐﻴﻞ أو‬ .‫اﻟﻀﻮﺿﺎء ﺑﻌﺪ اﻟﺘﺮﻛﻴﺐ‬ ‫• وﻓﻘ ﹰ ﺎ ﺨﻤﻟﻄﻂ ﺗﺮﻛﻴﺐ اﻟﻘﺎﻋﺪة، ﻗﻢ ﺑﺘﺜﺒﻴﺖ اﻟﻮﺣﺪة ﺑﺸﻜ ﻞ ﹴ ﻣﺤﻜﻢ ﺑﺎﺳﺘﻌﻤﺎل ﺑﺮاﻏﻲ اﻟﻘﺎﻋﺪة. )ﻗﻢ ﺑﺘﺤﻀﻴﺮ‬ (.‫...
  • Page 44 (1) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ‬ ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ‬ .«‫1( ﻋﻨﺪ ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ، راﺟﻊ »ﺗﻨﺒﻴﻬﺎت اﺣﺘﻴﺎﻃﻴﺔ ﺣﻮل اﺧﺘﻴﺎر اﳌﻮﻗﻊ« و»ﻣﺨﻄﻄﺎت ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ‬ .‫2( إذا ﻛﺎن اﻟﻘﻴﺎم ﺑﺄﻋﻤﺎل اﻟﺘﺼﺮﻳﻒ أﻣﺮ ﹰ ا ﺿﺮورﻳ ﹰ ﺎ، اﺗﺒﻊ اﻹﺟﺮاءات اﻟﻮاردة أدﻧﺎه‬ ‫أﻋﻤﺎل اﻟﺘﺼﺮﻳﻒ‬ .‫ﻟﻠﺘﺼﺮﻳﻒ‬...
  • Page 45 (2) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ‬ ‫ﺗﻔﺮﻳﻎ اﻟﻬﻮاء ﺑﺎﺳﺘﻌﻤﺎل ﻣﻀﺨﺔ اﻟﺘﻔﺮﻳﻎ واﻟﺘﺤﻘﻖ ﻣﻦ وﺟﻮد ﺗﺴﺮﻳﺐ ﻟﻠﻐﺎز‬ ‫ﲢﺬﻳﺮ‬ .‫( داﺧﻞ داﺋﺮة اﻟﺘﺒﺮﻳﺪ‬R32) ‫• ﻻ ﺗﻌﻤﺪ إﻟﻰ دﻣﺞ أي ﻣﻮاد أﺧﺮى ﻏﻴﺮ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ اﶈﺪد‬ .‫• إذا ﺣﺪث ﺗﺴﺮﻳﺐ ﻟﻐﺎز اﻟﺘﺒﺮﻳﺪ، ﻗﻢ ﺑﺘﻬﻮﻳﺔ اﻟﻐﺮﻓﺔ ﺑﺄﺳﺮع وﻗﺖ ﳑﻜﻦ ﻗﺪر اﳌﺴﺘﻄﺎع‬ .‫...
  • Page 46 (3) ‫ﺗﺮﻛﻴﺐ اﻟﻮﺣﺪة اﳋﺎرﺟﻴﺔ‬ ‫أﻋﻤﺎل ﲤﺪﻳﺪ أﻧﺎﺑﻴﺐ ﺳﺎﺋﻞ اﻟﺘﺒﺮﻳﺪ‬ ‫اﳉﺪار‬ ‫اﺣﺮص ﻋﻠﻰ‬ .‫وﺿﻊ ﻏﻄﺎء‬ ‫6-1 ﺗﻨﺒﻴﻬﺎت ﺣﻮل اﻟﺘﻌﺎﻣﻞ ﻣﻊ اﻷﻧﺎﺑﻴﺐ‬ ‫اﳌﻄﺮ‬ ‫ﻓﻲ ﺣﺎل ﻋﺪم ﺗﻮﻓﺮ ﻏﻄﺎء‬ .‫ﻗﻢ ﺑﺤﻤﺎﻳﺔ اﻟﻄﺮف اﳌﻔﺘﻮح ﻣﻦ اﻷﻧﺒﻮب ﻣﻦ اﻟﻐﺒﺎر واﻟﺮﻃﻮﺑﺔ‬ ‫اﻟﺘﻮﺳﻌﺔ، ﻗﻢ ﺑﺘﻐﻄﻴﺔ‬ ‫ﻓﺘﺤﺔ اﻟﺘﻮﺳﻌﺔ ﺑﺸﺮﻳﻂ‬ ‫ﻳﻨﺒﻐﻲ...
  • Page 47 (2) ‫ﲤﺪﻳﺪ اﻷﺳﻼك‬ .‫ﻛﻴﻔﻴﺔ ﺗﺮﻛﻴﺐ ﻟﻮﺣﺔ اﻟﺘﻘﺴﻴﻢ‬  ‫ﻗﻢ ﺑﺈدﺧﺎل ﻧﺘﻮء ﻟﻮﺣﺔ اﻟﺘﻘﺴﻴﻢ ﻓﻲ اﻟﺜﻠﻤﺔ‬ ‫اﻟﺒﺮاﻏﻲ‬ .‫اﳌﻮﺟﻮدة ﻋﻠﻰ اﻟﻠﻮح اﳌﻌﺪﻧﻲ‬ ‫ﻗﻢ ﺑﺰﻟﻖ ﻟﻮﺣﺔ اﻟﺘﻘﺴﻴﻢ ﺑﺤﻴﺚ ﻳﺘﻢ ﺗﺜﺒﻴﺖ‬ ‫اﻟﻠﺴﺎن اﳌﻮﺟﻮد ﻋﻠﻰ اﻟﻠﻮح اﳌﻌﺪﻧﻲ ﻓﻲ اﻟﻔﺘﺤﺔ‬ ‫ﻏﻄﺎء اﻟﺼﻴﺎﻧﺔ‬ .‫اﳌﻮﺟﻮدة ﻋﻠﻰ ﻟﻮﺣﺔ اﻟﺘﻘﺴﻴﻢ‬ .‫ﻗﻢ...
  • Page 48 ‫ﻋﻤﻠﻴﺔ اﻟﻀﺦ ﻟﻸﺳﻔﻞ‬ .‫ﳊﻤﺎﻳﺔ اﻟﺒﻴﺌﺔ، ﺗﺄﻛﺪ ﻣﻦ اﻟﻘﻴﺎم ﺑﺎﻟﻀﺦ ﻟﻸﺳﻔﻞ ﻋﻨﺪ إﻋﺎدة ﻧﻘﻞ اﻟﻮﺣﺪة أو اﻟﺘﺨﻠﺺ ﻣﻨﻬﺎ‬ .‫اﻧﺰع أﻏﻄﻴﺔ اﻟﺼﻤﺎم ﻣﻦ ﺻﻤﺎم إﻳﻘﺎف اﻟﺴﺎﺋﻞ وﺻﻤﺎم إﻳﻘﺎف اﻟﻐﺎز‬ ‫ﻣﻔﺘﺎح ﺷﺪ‬ .‫ﻗﻢ ﺑﺘﻨﻔﻴﺬ ﻋﻤﻠﻴﺔ اﻟﺘﺒﺮﻳﺪ اﻟﻘﺴﺮي‬ ‫ﺳﺪاﺳﻲ‬ .‫دﻗﺎﺋﻖ، ﻗﻢ ﺑﺈﻏﻼق ﺻﻤﺎم إﻳﻘﺎف اﻟﺴﺎﺋﻞ ﺑﺎﺳﺘﻌﻤﺎل ﻣﻔﺘﺎح ﺷﺪ ﺳﺪاﺳﻲ‬ ‫إﻟﻰ‬...