14 POINT I/O 24V DC Expansion Power Supply
General
Attribute
Field power bus, supply voltage
range
Field power bus, supply current, max
Isolation voltage
Enclosure type rating
Conductor size
(1)
Conductor category
(1)
Use this Conductor Category information for planning conductor routing. Refer to publication 1770-4.1, Industrial
Automation Wiring and Grounding Guidelines.
Environmental Specifications
Attribute
Temperature, operating
Temperature, storage
Relative humidity
Vibration
Shock, operating
Shock, non-operating
Emissions
Publication 1734-IN058C-EN-P - October 2015
Value
10...28.8V DC
10 A
50V continuous, tested to withstand 2600V DC for 60 s
None (open-style)
0.324...2.08 sq. mm (#22...#14 AWG) solid or stranded copper
wire rated @ 75 °C or greater
1.2 mm (3/64 inch) insulation max
1 – on power ports
Value
IEC 60068-2-1 (Test Ad, operating cold),
IEC 60068-2-2 (Test Bd, operating dry heat),
IEC 60068-2-14 (Test Nb, operating thermal shock)
-20...55 °C (-4...131 °F)
IEC60068-2-1 (Test Ab, unpackaged non-operating cold)
IEC60068-2-2 (Test Bb, unpackaged non-operating dry heat)
IEC60068-2-14 (Test Na, unpackaged non-operating thermal shock)
-40...85 °C (-40...185 °F)
IEC60068-2-30 (Test Db, unpackaged damp heat)
5...95% non-condensing
IEC 60068-2-6 (Test Fc, operating):
5 g @ 10...500 Hz
IEC60068-2-27 (Test Ea, unpackaged shock):
30 g
IEC60068-2-27 (Test Ea, unpackaged shock):
50 g
CISPR 11: