Zic-4A Two-Channel Audio Wiring - Siemens ZIC-4A Installation Instructions Manual

Zone indicating card
Table of Contents

Advertisement

Zone Wiring
STYLE Z
ZONE 3
(CLASS A)
CHANNEL A
TO NEXT
ZIC-4A
CHANNEL B
NOTES
1. All wiring must be in accordance with Article 760 of NEC or local building codes. Wiring for each zone can either be Class A or Class B.
2. All output circuits are power limited to NFPA 70 per NEC 760.
3. Electrical Ratings:
Output Zone Supervisory: 4mA max
Output Zone Active:
4. EOL resistor, 24k ohms, 1 watt , 5%, P/N 140-033771.
5. Polarity shown in active state.
6. Sync and non-sync notification appliances permitted.
7 . For a list of Compatible Notification Appliances, refer to P/N 315-096363.
8. Refer to CAB1/CAB1R (P/N 315-0330007) and CAB2-BB/CAB3-BB (P/N 315-033009) Installation Instructions for details on the separation of
power limited and non-power limited wiring.
9. Verify that P1 - P4 are in the proper location for speaker application.
10. Positive or negative ground fault detected at <40K ohms for
terminals 1-16.
Figure 12

ZIC-4A Two-Channel Audio Wiring

Siemens Industry, Inc.
Building Technologies Division
ZONE 1
STYLE Z
CLASS A
24K,
1W
5%
1
2
3
4
9
10
11
12
24K,
1W
5%
ONE SLOT OF CC-5
17
18
19
96 Watts max / zone
ZONE 2
24K,
STYLE Y
1W
CLASS B
5%
NC
NC
5
6
7
8
13
14
15
16
NC
NC
20
21
22
23
24
17
STYLE Y
ZONE 4
(CLASS B)
24K,
1W
5%
AUDIO FROM PREVIOUS
ZIC-4A OR FROM ZAC-40/
ZAM-180 TERMINALS
1A AND 1B OR 2A AND 2B
P/N 315-033050-15