Operation and Installation Instructions
MODEL ZS-30
Intrinsically Safe Module

Operation

SIEMENS
Item Name and
Model Number
NON-HAZARDOUS LOCATION EQUIPMENT
Model ZS-30
Zone module (P/N 515-022079)
Model 515-180238
Diode shunt safety barrier
HAZARDOUS LOCATION EQUIPMENT
Detector DI-3IS
Detector S121
Detector S122
Base DB-3
For use with DI-3IS
Cable 465-514391
Limited-energy shielded cable
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-024056-17
(P/N 515-180238)
(Optional)

NEC Hazardous Location Classification

Class I:
Class II:
Class Ill:
Division 1:
Group A:
Group B:
Group C:
Group D:
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
Fire Safety

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZS-30 and is the answer not in the manual?

Questions and answers

Summary of Contents for Siemens ZS-30

  • Page 1 For use with DI-3IS Cable 465-514391 Limited-energy shielded cable (Optional) Group C: Group D: Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 CN P/N 315-024056-17...
  • Page 2 Group E Group F: Group G: Description Installation System 3 chassis ground must be removed. Figure 1 Field Assembly of Diode Barrier...
  • Page 3 Maximum Maximum Capacitance Inductance Excluding Detector in mH Capacitance in µF Group A Group B Group C,E,F Group D,G Figure 2 Barrier Label Note: FM Control Document – there are to be no changes to this document without prior Factory Mutual approval.
  • Page 4 SHORT CIRCUIT CURRENT 30 mA 7. ONLY MECHANICAL (NON-ENERGY STORING) SHORTING DEVICES SUCH AS 2. WHEN ZS-30 IS USED, SYSTEM CHASSIS GROUND CONNECTION MUST BE THE MS-51 MANUAL STATION MAY BE USED. REMOVED AND TERMINALS 5 AND 7 OF DIODE SHUNT BARRIER MUST BE 8.

Table of Contents