ELECTRICAL CONNECTIONS
4
Figure 4-7: Connection of remote version
1 Terminal connection of flow sensor
2 Terminal connection of signal converter
3 Terminal end pair shielding of flow sensor
4 Filler wire pair shielding (protected with heat shrink tubing)
5 Fork clamp pair shielding on signal converter side
6 Heat shrink tubing
The maximum cable length is 50 m / 164 ft.
The cable can be shortened easily. All wires must be connected afterwards.
CAUTION!
Please ensure that the shielding 4 has been properly connected to both terminals 3 and 5. The
exterior shielding of the cable must not be connected to any terminal.