INSTALLATION
3

3.4.1 Prohibited installation when measuring liquids

Figure 3-3: Upper pipe bend
CAUTION!
Prohibited: Installing the device in an upper pipe bend 1, because there is a risk of gas bubbles
2 forming. Gas bubbles can lead to pressure surges and inaccurate measurement.
Figure 3-4: Downstream pipe and outlet
CAUTION!
Installing the device in a downstream pipe 3 or upstream pipe of an outlet 4. There is the risk of
partially filled pipes leading to inaccurate measurements.
24
www.siemens.com/flow
SITRANS FX330
05/2016 - A5E36751269-AA