SITRANS FX330
Status
Event group
type
F
Sensor
F
Electronics
05/2016 - A5E36751269-AA
Single event
Fatal Sensor Error
No Temperature Sensor
Sensor Comm. Error
No/Invalid Pressure Sensor
Corrupt Sensor Parameter
Temperature Sensor Error
No Measurement Value
Fatal Converter Error
CO DM Error
CO DDM Error
CO Unknown Error
CO ADC Error
Internal Comm. Error
Inconsistent Parameters
Sensor Comm. Error
Power Supply Error
Sensor/Conv. FW Mismatch
Max. Number of Restarts
www.siemens.com/flow
Description
An internal error in the
sensor module has occured.
The internal temperature
sensor (PT1000) is not
connected or its resistance
is too high. The process
temperature cannot be
measured.
Error in the internal bus
communication or hardware
failure.
Pressure sensor not
available or invalid
communication
Flow sensor parameters are
inconsistent
The resistance of the
internal temperature sensor
(PT1000) is too low.
No connection to flow
sensor
An electronics or hardware
failure has occured.
Internal electronic failure
Internal electronic failure
Internal electronic failure
Internal electronic failure
Error in the internal bus
communication.
Inconsistent data in the
parameter memory after
®
editing via HART
interface
Error in the internal bus
communication or hardware
failure
Internal voltage too low to
switch on sensor power
supply
Incompatible firmware
versions in the sensor and
the converter module
The device could not start
the measuring mode after a
cold starting.
OPERATION
Actions to eliminate the
event
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Check the pick-up and its
connection. Contact the
manufacturer, if necessary.
For remote version: Check
the sensor connection.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Check the connection of the
pressure sensor. Perform a
hard reset. If the message
recurs, contact the
manufacturer.
Check flow sensor
parameters.
Check the pick-up and its
connection. Perform a hard
reset. Contact the
manufacturer, if necessary.
Contact the manufacturer.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Check the parameters and
make sure that the set of
data is consistent. Additional
information on the error can
®
be called via HART
interface.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Check power supply
connection or replace the
electronics.
Perform a hard reset. If the
message recurs, contact the
manufacturer.
Perform a hard reset once
again. If the message
recurs, contact the
manufacturer.