Siemens SITRANS FX330 Operating Instructions Manual

Siemens SITRANS FX330 Operating Instructions Manual

Sitrans f series vortex flowmeters
Table of Contents

Advertisement

SITRANS F
Vortex flowmeters
SITRANS FX330
Operating Instructions
Edition
05/2016
Answers for industry.

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS FX330

  • Page 1 SITRANS F Vortex flowmeters SITRANS FX330 Operating Instructions Edition 05/2016 Answers for industry.
  • Page 2 IMPRINT :::::::::::::::::::::::::::::::::: All rights reserved. It is prohibited to reproduce this documentation, or any part thereof, without the prior written authorisation of Siemens. Subject to change without notice. Copyright 2016 by Siemens www.siemens.com/flow 05/2016 - A5E36751269-AA...
  • Page 3: Table Of Contents

    CONTENTS SITRANS FX330 1 Safety instructions 1.1 Software history ....................... 6 1.2 Intended use ........................7 1.3 Certifications ........................9 1.4 Safety instructions from the manufacturer ..............10 1.4.1 Copyright and data protection ....................10 1.4.2 Disclaimer ..........................10 1.4.3 Product liability and warranty ....................11 1.4.4 Information concerning the documentation.................
  • Page 4 CONTENTS SITRANS FX330 4 Electrical connections 4.1 Safety instructions......................36 4.2 Connecting the signal converter ..................37 4.3 Electrical connections ....................38 4.3.1 Power supply......................... 38 4.3.2 Current output ........................38 4.3.3 Current input......................... 39 4.3.4 Binary output......................... 39 4.3.5 Limit switch output ....................... 40 4.3.6 Pulse output / Frequency output ..................
  • Page 5 CONTENTS SITRANS FX330 7 Service 7.1 Replacing signal converter / LC display ................ 92 7.2 Maintaining the O-rings....................93 7.3 Spare parts availability....................94 7.4 Availability of services ....................94 7.5 Return procedure ......................94 7.6 Disposal .......................... 95 8 Technical data 8.1 Functional principle......................
  • Page 6: Safety Instructions

    SAFETY INSTRUCTIONS SITRANS FX330 1.1 Software history The "Electronic Revision" (ER) is consulted to document the revision status of electronic equipment according to NE 53 for all devices. It is easy to see from the ER whether troubleshooting or larger changes in the electronic equipment have taken place and how that has affected the compatibility.
  • Page 7: Intended Use

    SAFETY INSTRUCTIONS SITRANS FX330 1.2 Intended use CAUTION! Responsibility for the use of the measuring devices with regard to suitability, intended use and corrosion resistance of the used materials against the measured fluid lies solely with the operator. INFORMATION! This device is a Group 1, Class A device as specified within CISPR11:2009. It is intended for use in industrial environment.
  • Page 8 SAFETY INSTRUCTIONS SITRANS FX330 The devices are rated for the following flow velocities: Liquids: : 0.25 m/s 0.8 ft/s DN15...DN300 : 10 m/s 32 ft/s Gases and DN15 : 3 m/s 10 ft/s steam: : 45 m/s 147 ft/s DN15C...
  • Page 9: Certifications

    SAFETY INSTRUCTIONS SITRANS FX330 1.3 Certifications CE marking The device fulfils the statutory requirements of the following EU directives: • Pressure equipment directive • EMC directive • Devices for use in hazardous areas: ATEX directive as well as • EN 61010 •...
  • Page 10: Safety Instructions From The Manufacturer

    SAFETY INSTRUCTIONS SITRANS FX330 1.4 Safety instructions from the manufacturer 1.4.1 Copyright and data protection The contents of this document have been created with great care. Nevertheless, we provide no guarantee that the contents are correct, complete or up-to-date. The contents and works in this document are subject to copyright. Contributions from third parties are identified as such.
  • Page 11: Product Liability And Warranty

    SAFETY INSTRUCTIONS SITRANS FX330 1.4.3 Product liability and warranty The operator shall bear responsibility for the suitability of the device for the specific purpose. The manufacturer accepts no liability for the consequences of misuse by the operator. Improper installation or operation of the devices (systems) will cause the warranty to be void. The respective "Standard Terms and Conditions"...
  • Page 12: Warnings And Symbols Used

    SAFETY INSTRUCTIONS SITRANS FX330 1.4.5 Warnings and symbols used Safety warnings are indicated by the following symbols. DANGER! This warning refers to the immediate danger when working with electricity. DANGER! This warning refers to the immediate danger of burns caused by heat or hot surfaces.
  • Page 13: Device Description

    DEVICE DESCRIPTION SITRANS FX330 2.1 Scope of delivery INFORMATION! Inspect the packaging carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer. INFORMATION! Do a check of the packing list to make sure that you have all the elements given in the order.
  • Page 14: Devices With Connection Flange

    DEVICE DESCRIPTION SITRANS FX330 2.2.1 Devices with connection flange Figure 2-2: Flanged devices with display 1 Version with temperature sensor 2 Version with temperature sensor and optional pressure sensor 3 Version with temperature sensor, optional pressure sensor and shut-off valve 4 Version with temperature sensor, flow sensor with integrated reducer 2.2.2 Devices in sandwich version...
  • Page 15: Dual Version And Twofold Reliability

    DEVICE DESCRIPTION SITRANS FX330 2.2.3 Dual version and twofold reliability This is a genuine redundant system with two independent flow sensors and two signal converters. This provides twofold functional reliability and availability of the measurement. This variant is ideally suited for measurements in multi- product pipelines.
  • Page 16: Devices With Integrated Nominal Diameter Reduction

    DEVICE DESCRIPTION SITRANS FX330 2.2.5 Devices with integrated nominal diameter reduction The device versions F1R and F2R offer an integrated nominal diameter reduction up to two nominal diameter sizes to assure best results in accuracy and optimum measuring ranges; even in pipelines with large diameters, which have been designed for a low pressure loss.
  • Page 17: Free Air Delivery Measurement - Fad (Optional)

    DEVICE DESCRIPTION SITRANS FX330 2.2.7 Free air delivery measurement - FAD (optional) To create compressed air, a compressor draws in air from the ambient atmosphere, compresses it and delivers it at the required pressure. Since the ambient atmosphere also contains water vapour, what the compressor draws in is a mixture of air and water vapour. In addition to the moisture in the air, the ambient temperature and pressure conditions on the inlet side and the process conditions on the outlet side also influence compressor capacity.
  • Page 18: Gross Heat Quantity Calculation (Optional)

    DEVICE DESCRIPTION SITRANS FX330 2.2.8 Gross heat quantity calculation (optional) This feature enables the calculation of the heat flow volume in systems where hot water, saturated or superheated steam is used for heating. The determination of gross heat is based on the relation between the temperature-dependent enthalpy of steam and mass flow.
  • Page 19: Net Heat Quantity Calculation (Optional)

    DEVICE DESCRIPTION SITRANS FX330 2.2.9 Net heat quantity calculation (optional) When measuring the net heat, the energy consumption of steam and hot water can be exactly determined. To do this, the vortex flowmeter is built into the inlet run of the plant component to be measured.
  • Page 20: Dual Seal

    DEVICE DESCRIPTION SITRANS FX330 2.2.10 Dual seal To comply with the requirements of ANSI/ISA 12.27.01 "Requirements for Process Sealing Between Electrical Systems and Flammable or Combustible Process Fluids", a membrane vent is integrated in the neck of the device. This vent is located between the primary seal (process)
  • Page 21: Nameplate

    DEVICE DESCRIPTION SITRANS FX330 2.3 Nameplate INFORMATION! Check the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate. Figure 2-8: Example of nameplate 1 Meter type...
  • Page 22: Installation

    INSTALLATION SITRANS FX330 3.1 General notes on installation INFORMATION! Inspect the packaging carefully for damages or signs of rough handling. Report damage to the carrier and to the local office of the manufacturer. INFORMATION! Do a check of the packing list to make sure that you have all the elements given in the order.
  • Page 23: Installation Conditions

    INSTALLATION SITRANS FX330 3.4 Installation conditions INFORMATION! For accurate volumetric flow measurement the measuring device needs a completely filled pipe and a fully developed flow profile. CAUTION! Any vibration will distort the measuring result. That is why any vibrations in the pipeline must be prevented through suitable measures.
  • Page 24: Prohibited Installation When Measuring Liquids

    INSTALLATION SITRANS FX330 3.4.1 Prohibited installation when measuring liquids Figure 3-3: Upper pipe bend CAUTION! Prohibited: Installing the device in an upper pipe bend 1, because there is a risk of gas bubbles 2 forming. Gas bubbles can lead to pressure surges and inaccurate measurement.
  • Page 25: Prohibited Installation When Measuring Steam And Gases

    INSTALLATION SITRANS FX330 3.4.2 Prohibited installation when measuring steam and gases 1 Lower pipe bends 2 Condensate DANGER! Prohibited: Installing the device in a lower pipe bend 1, because there is a risk of condensate forming 2. Condensate can lead to cavitation and inaccurate measurement. Under certain circumstances the device can be destroyed and the measured medium can leak.
  • Page 26: Preferred Mounting Position

    INSTALLATION SITRANS FX330 3.4.4 Preferred mounting position Preferred mounting position Figure 3-6: Mountig position 1 Above a horizontal pipe 2 Underneath a horizontal pipe (not permitted with lines at risk of condensate forming) 3 On a vertical pipe 4 Horizontal pipeline with signal converter-orientation 90° to the side...
  • Page 27: Minimum Inlet Sections

    INSTALLATION SITRANS FX330 3.5 Minimum inlet sections Figure 3-7: Inlet sections 1 General inlet section without disturbing flow ≥ 15 DN 2 After a control valve ≥ 50 DN 3 After a pipe diameter reduction ≥ 20 DN 4 After a single bend 90° ≥ 20 DN 5 After a double bend 2x90°...
  • Page 28: Minimum Outlet Sections

    INSTALLATION SITRANS FX330 3.6 Minimum outlet sections Figure 3-8: Minimum outlet sections 1 Upstream of pipe expanders, pipe bends, control valves, etc. ≥ 5 DN 2 Upstream of measuring points ≥ 5 DN INFORMATION! The interior of the pipe at the metering points must be free of burrs and other flow impediments.
  • Page 29: Installation

    INSTALLATION SITRANS FX330 3.8 Installation 3.8.1 General installation notes CAUTION! Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. The regional occupational health and safety directives must always be observed. The following procedures have to be carried out before installing the device: •...
  • Page 30: Installing Devices In Sandwich Design

    INSTALLATION SITRANS FX330 3.8.2 Installing devices in sandwich design Figure 3-12: Installation using centering ring 1 Flow sensor 2 Centering ring 3 Bolts with fixing nuts 4 Drill hole 5 Sealing • Push the first bolt 3 through the hole 4 of both flanges.
  • Page 31: Installing Devices In Flange Design

    INSTALLATION SITRANS FX330 3.8.3 Installing devices in flange design Figure 3-13: Installing devices in flange design 1 Sealing 2 Bolts with fastening nuts • Use bolts and fastening nuts 2 to attach the measuring device to one side of the flange.
  • Page 32: Mounting The Field Housing, Remote Version

    INSTALLATION SITRANS FX330 3.8.4 Mounting the field housing, remote version INFORMATION! Assembly materials and tools are not part of the delivery. Use the assembly materials and tools in compliance with the applicable occupational health and safety directives. Pipe mounting Figure 3-14: Pipe mounting of the field housing 1 Fix the signal converter to the pipe.
  • Page 33: Heat Insulation

    INSTALLATION SITRANS FX330 3.9 Heat insulation CAUTION! For applications with medium temperatures above +160 ° C / +320 ° F an insulation of the pipeline in accordance to the insulation guideline is suggested. Avoid higher electronic temperatures than +80 C / +176 °...
  • Page 34: Turning The Connection Housing

    INSTALLATION SITRANS FX330 3.10 Turning the connection housing DANGER! All work on the device electronics may only be carried out by appropriately trained personnel. The regional occupational health and safety directives must always be observed. Figure 3-17: Turning the connection housing 1 M4 Allen screw on connection housing •...
  • Page 35: Turning The Display

    INSTALLATION SITRANS FX330 3.11 Turning the display DANGER! All work on the device electronics may only be carried out by appropriately trained personnel. The regional occupational health and safety directives must always be observed. INFORMATION! If the measuring device is installed in a vertical pipe, you will have to turn the display by 90 ;...
  • Page 36: Electrical Connections

    ELECTRICAL CONNECTIONS SITRANS FX330 4.1 Safety instructions DANGER! All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate (for details refer to Nameplate on page 21...
  • Page 37: Connecting The Signal Converter

    ELECTRICAL CONNECTIONS SITRANS FX330 4.2 Connecting the signal converter DANGER! All work on the electrical connections may only be carried out with the power disconnected. Take note of the voltage data on the nameplate! INFORMATION! When using the binary output M1...M4 as pulse output and frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from electrical interferences (EMC).
  • Page 38: Electrical Connections

    ELECTRICAL CONNECTIONS SITRANS FX330 4.3 Electrical connections The signal converter is a 2-wire device with 4...20 mA as output signal. All other inputs and outputs are passive and always require an additional power supply. 4.3.1 Power supply All versions are intended for connection to limited-energy circuits of max. 36 VDC / 4 A.
  • Page 39: Current Input

    ELECTRICAL CONNECTIONS SITRANS FX330 4.3.3 Current input An external transmitter, e.g. temperature or pressure transmitter, can be connected to terminals I1+ and I2-. The 4...20 mA current signal is converted to the corresponding temperature or pressure value in the signal converter.
  • Page 40: Limit Switch Output

    ELECTRICAL CONNECTIONS SITRANS FX330 4.3.5 Limit switch output Figure 4-4: Connection binary output 1 Power supply U ext. 2 Isolated switching amplifier INFORMATION! Binary output Mx can only be operated if the loop supply 4...20 mA is applied to the terminals C1+ and C2-.
  • Page 41 ELECTRICAL CONNECTIONS SITRANS FX330 Value range for NAMUR NC contact 1 NO contact 2 Switching value reached < 1 mA > 3 mA Switching value not reached > 3 mA < 1 mA 1 C2.2.6 Invert Signal On 2 C2.2.6 Invert Signal Off...
  • Page 42: Pulse Output / Frequency Output

    ELECTRICAL CONNECTIONS SITRANS FX330 4.3.6 Pulse output / Frequency output The maximum frequency of both pulse output and frequency output is 1000 Hz. Figure 4-5: Electrical connection pulse output 1 Signal converter power supply 2 Pulse output power supply 3 Pulse counter or frequency meter The connection is made between terminal M2/4 Common (-) and M1 for Hi Current (+) or M3 NAMUR (+).
  • Page 43: Status Output

    ELECTRICAL CONNECTIONS SITRANS FX330 4.3.7 Status output The + pole of the high current output is on the M1 terminal connection. The + pole of the NAMUR output is on the M3 connection terminal. Terminal M2/4 is the common - pole of the status output.
  • Page 44 ELECTRICAL CONNECTIONS SITRANS FX330 Figure 4-7: Connection of remote version 1 Terminal connection of flow sensor 2 Terminal connection of signal converter 3 Terminal end pair shielding of flow sensor 4 Filler wire pair shielding (protected with heat shrink tubing)
  • Page 45: Grounding Connections

    ELECTRICAL CONNECTIONS SITRANS FX330 4.5 Grounding connections The grounding can be done either by connecting the PE (Protective Earth) terminal in the housing or the PE terminal on the connection piece between flow sensor and signal converter. Both of these electrical connections are equally effective from a technical point of view.
  • Page 46: Ingress Protection

    ELECTRICAL CONNECTIONS SITRANS FX330 4.6 Ingress protection The signal converter electronics housing meets the requirements for IP66/67 in accordance with EN 60529 both for the compact and for the remote version. CAUTION! After all servicing and maintenance work on the measuring device, the specified ingress protection category must be ensured again.
  • Page 47: Start-Up

    START-UP SITRANS FX330 5.1 Start-up screen INFORMATION! After connection to power supply the device carries out a self-test. After 10 seconds the following start-up screen appears: Figure 5-1: Start-up screen After finishing of the self-test the device switches to the measuring mode. Here, all of the parameters preset for the customer are analysed and checked for plausibility, and the currently measured value is displayed.
  • Page 48: Operation

    OPERATION SITRANS FX330 6.1 Display and operating elements In case of an open front cover, the device is operated by using mechanical keys; in the case of a closed cover, a bar magnet 1 is used. Figure 6-1: Pen with bar magnet...
  • Page 49: Display For Selection Of Submenu And Functions, 3 Lines

    OPERATION SITRANS FX330 The mechanical keys and keys for the bar magnet have the same functionality. In this documentation the keys are represented as symbols to describe the operating functions: Mechanical and bar magnet Symbol → ↓ ↑ Table 6-1: Description of keys...
  • Page 50: Display When Setting Parameters, 4 Lines

    OPERATION SITRANS FX330 6.1.2 Display when setting parameters, 4 lines Figure 6-5: Display when setting parameters, 4 lines 1 Current menu(s), submenu or function 2 Number relating to 7 3 Denotes factory setting 4 Denotes permissible value range 5 Permissible value range for numeric values 6 Currently set value, unit or function (when selected, appears with white text, blue background) This is where the data is changed.
  • Page 51: Basic Principles Of Operation

    OPERATION SITRANS FX330 6.2 Basic principles of operation 6.2.1 Functional description of the keys INFORMATION! It is recommended to activate the push buttons perpendicular to the front. Touching them • from the side can cause incorrect operation. The mechanical keys and keys for the bar magnet have the same functionality.
  • Page 52: Character Selection In Change Mode

    OPERATION SITRANS FX330 Save Configuration? Changes are accepted. ^ ^ ^ ^ An update is carried out and the display returns to measuring mode. Save Configuration? Changes are discarded. ^ ^ ^ ^ The display returns to measuring mode. Save Configuration?
  • Page 53: Units, Figures And Factors

    OPERATION SITRANS FX330 6.2.5 Units, figures and factors Numerical values and factors are displayed in a 8 digit format. Numerical values are either displayed in floating point format (12345678) or are expressed in exponential format (12.345e06). Exponents are used in following steps: 03 / 06 / 09 or -03 / -06 / -09 etc. The conversion factor of the totalizer and the pulse output, however, is expressed in whole numbers.
  • Page 54 OPERATION SITRANS FX330 The table below lists the access levels, their default passwords and associated permissions. Access level Access level Access level Access level Default password Default password Default password Default password Permissions Permissions Permissions Permissions • User 0000 View device information (any unassigned •...
  • Page 55: Overview Of The Most Important Functions And Units

    OPERATION SITRANS FX330 6.3 Overview of the most important functions and units INFORMATION! A complete list of all functions and short descriptions is provided in the next section. All default parameters and settings are adapted for the customer. Menu structure •...
  • Page 56: Gas Options For Gas Measurement

    OPERATION SITRANS FX330 6.5 Gas options for gas measurement Gases can be selected in menu "A8, C1.2 Medium" or "C1.3.1 Gas Mixture". For fluid selection gas, wet gas or gas mixture the following gas selection is available: Ammonia Argon i-Butane...
  • Page 57: Units

    OPERATION SITRANS FX330 6.6 Units The following units can be selected and set in menu A9 and/or C6.5. Furthermore, for each measurement customised units can be defined. Units for volume flow Units for volume flow Units for volume flow Units for volume flow...
  • Page 58 OPERATION SITRANS FX330 Units for mass flow Units for mass flow Units for mass flow Units for mass flow /min Customised mass flow Table 6-7: Flow measurements and their units Totalizer units Totalizer units Totalizer units Totalizer units Volume Norm./standard* volume...
  • Page 59 OPERATION SITRANS FX330 Units additional measurements Units additional measurements Units additional measurements Units additional measurements Temperature Pressure Power Energy Density °C mbar kg/m °F kg/L kJ/h g/cm °Rank MJ/s kW*h kg/m Customised MJ/h Mcal g/ml kg/cm temperature Mcal/h lb/gal g/cm...
  • Page 60: Menu Structure

    OPERATION SITRANS FX330 6.7 Menu structure 6.7.1 Menu overview "A Quick Setup" Meas. Menu A Submenus ↓ ↑ ↓ ↑ ↓ ↑ > ^ > ^ > ^ A Quick Setup A1 Language A2 Contrast A3 Login A4 Tag A5 Long Tag...
  • Page 61: Menu Overview "B Test

    OPERATION SITRANS FX330 6.7.2 Menu overview "B Test" Meas. Menu B Submenus ↓ ↑ ↓ ↑ ↓ ↑ ↓ ↑ > > ^ > ^ > ^ > ^ B Test B1 Simulation B1.1 Set Value B1.1.1 Volume Flow B1.1.2 Norm. Volume Flow B1.1.3 Mass Flow...
  • Page 62: Menu Overview "C Setup

    OPERATION SITRANS FX330 Meas. Menu B Submenus ↓ ↑ ↓ ↑ ↓ ↑ ↓ ↑ > > ^ > ^ > ^ > ^ B Test B2 Actual B2.16 Pressure Values B2.17 Vortex Frequency B2.18 Velocity B2.19 Specific Enthalpy B2.20 Specific Heat Cap.
  • Page 63 OPERATION SITRANS FX330 Meas. Menu C Submenus ↓ ↑ ↓ ↑ ↓ ↑ ↓ ↑ > > ^ > ^ > ^ > ^ C Setup C2 Output C1.11 Normal Values C1.11.1 Norm. Temperature C1.11.2 Norm. Pressure C1.11.3 Norm. Density C2.1 Current Output...
  • Page 64 OPERATION SITRANS FX330 Meas. Menu C Submenus ↓ ↑ ↓ ↑ ↓ ↑ ↓ ↑ > > ^ > ^ > ^ > ^ C Setup C5 Display C5.1 Language C5.2 Contrast C5.3 1. Meas. Page C5.3.1 Function C5.3.2 Measurement 1. Line C5.3.3 0% Range...
  • Page 65 OPERATION SITRANS FX330 Meas. Menu C Submenus ↓ ↑ ↓ ↑ ↓ ↑ ↓ ↑ > > ^ > ^ > ^ > ^ C Setup C6 Device C6.3 Extras C6.3.1 Meter Type C6.3.2 Heat C6.3.3 Heat & Dens. by Pres.
  • Page 66: Menu Description "A Quick Setup

    OPERATION SITRANS FX330 6.7.4 Menu description "A Quick Setup" Function Setting / Description A1 Language Available display languages: German, English and French Menu languages 22 more languages in preparation (for details refer to on page 55) A2 Contrast Adjust contrast of local display (-10...+10; Standard = 0) A3 Login Enter password: 0000 (to change password refer to menu C6.2.2)
  • Page 67 OPERATION SITRANS FX330 A11 Application Assistant The factory settings of the vortex flowmeter have been made in accordance with the order specifications. Nonetheless it can be necessary to make additional settings for the use of some functionalities. For an easy operation the device is equipped with an application assistant for each type of application.
  • Page 68 OPERATION SITRANS FX330 A11.1 Application Assistant - Liquid Function Setting / Description .2 Units .2.1 Volume Flow Select unit (default: according to order specification or m /h). .2.2 Mass Flow Select unit (default: according to order specification or kg/h). .2.3 Volume Select unit (default: according to order specification or m .2.4 Mass...
  • Page 69 OPERATION SITRANS FX330 A11.2 Application Assistant - Saturated Steam Function Setting / Description .2 Units Same options as in A11.1.2. .3 Process .3.1 Fluid Select "Steam". .3.2 Medium Select "Saturated Steam". .3.3 Time Constant 0...100 s .3.4 Low Flow Cutoff Enter low flow cutoff point in current volume flow unit.
  • Page 70 OPERATION SITRANS FX330 A11.3 Application Assistant - Superheated Steam Function Setting / Description This application assistant is available if meter type is set to "Heat & Dens. by Pres." or "Heat & Dens. & FAD" (refer to "C6.3 Extras"). .2 Units Same options as in A11.1.2.
  • Page 71 OPERATION SITRANS FX330 A11.4 Application Assistant - Heat Measurement Function Setting / Description This application assistant is available if meter type is not set to "Standard" (refer to "C6.3 Extras"). .2 Units .2.1 Volume Flow Select unit (default: according to order specification or m /h).
  • Page 72 OPERATION SITRANS FX330 Function Setting / Description .15 1. Meas. Page Same options as in A11.1.13. .16 2. Meas. Page Same options as in A11.1.14. A11.5 Application Assistant - Gas Function Setting / Description .2 Units Same options as in A11.1.2.
  • Page 73 OPERATION SITRANS FX330 Function Setting / Description .17 1. Meas. Page Same options as in A11.1.13. .18 2. Meas. Page Same options as in A11.1.14. A11.6 Application Assistant - FAD Function Setting / Description This application assistant is available if meter type is set to "Heat & Dens. & FAD" (refer to "C6.3 Extras").
  • Page 74: Menu Description "B Test

    OPERATION SITRANS FX330 6.7.5 Menu description "B Test" Menu overview "B Test" For simulation and actual values refer to on page 61. 6.7.6 Menu description "C Setup" Menu overview "C Setup" For further information refer to on page 62. There are four different meter types (software versions) available for the signal converter:...
  • Page 75 OPERATION SITRANS FX330 Function Setting / Description C1 Process C1.3.8 Compressor RPM Enter compressor revolutions per minute. C1.3.9 Rated Compr. RPM Enter rated compressor revolutions per minute. C1.4 Saturated Steam This menu is available, if fluid = "Steam" and medium = "Saturated Steam".
  • Page 76 OPERATION SITRANS FX330 Function Setting / Description C2 Output Technical data C2.1 Current Output 2-wire current output 4..20 mA (for details refer to on page 97) C2.1.1 Current Out. Meas. Determination of measurement variable for current output. Measurement variable for current output is pre-set according to application data.
  • Page 77 OPERATION SITRANS FX330 Function Setting / Description C2 Output C2.2.3 Frequency Output Only available, if "Frequency" is selected in C2.2.1. C2.2.3.1 Frequency Out. Select: Volume Flow / Norm. Volume Flow / Mass Flow / Density / Temperature1 / Meas. Temperature2 / Pressure / Vortex Frequency / Velocity / Specific Enthalpy / Specific Heat Capacity / Reynolds Number / FAD / Net Power / Gross Power Availability of selection depending on meter type and medium configuration.
  • Page 78 Entry will be displayed in the header bar on the LC display (depending on letter size, min. 11 digits can be displayed). C3.1.2.4 Manufacturer ID ® HART Manufacturer ID = 00042 (0x2A) [SIEMENS] (read-only) C3.1.2.5 Device Type Device Type = 00058 (0x3A) (read-only) C3.1.2.6 Device ID Individual device ID (read-only) C3.1.2.7 Universal Revision...
  • Page 79 OPERATION SITRANS FX330 Function Setting / Description C3 Communication C3.1.5.3 Slave Device ID Enter source slave address C3.1.5.4 Capture Command Select source command number: 1 / 2 / 3 / 9 / 33 C3.1.5.5 Slot Number Describes slot to process in response message. Select 1…8 (depending on source command number).
  • Page 80 OPERATION SITRANS FX330 Function Setting / Description C5 Display C5.1 Language Available display languages: German, English and French 22 more languages in preparation (for details refer to Menu languages on page 55) C5.2 Contrast Adjust contrast of local display (-10...+10).
  • Page 81 Display of meter type as activated in A10 or C6.3.2...C6.3.4 (read-only). C6.1.4 Serial Number Individual device ID (read-only). C6.1.5 Manufacturer ID ® HART Manufacturer ID = 00042 (0x2A) [SIEMENS] (read-only) C6.1.6 Device Name SITRANS FX330 (read-only) C6.1.7 V Number Internal order number (read-only). C6.1.8 Electronic Revision...
  • Page 82 OPERATION SITRANS FX330 Function Setting / Description C6 Device 6.5.9 Volume 6.5.10 Cst. Volume 6.5.11 Norm. Volume 6.5.12 Cst. Norm. Volume 6.5.13 Mass 6.5.14 Cst. Mass 6.5.15 Energy 6.5.16 Cst. Energy 6.5.17 Pressure 6.5.18 Cst. Pressure 6.5.19 Temperature 6.5.20 Cst. Temperature 6.5.21 Density...
  • Page 83: Setting Examples

    OPERATION SITRANS FX330 6.8 Setting examples 6.8.1 Settings for free air delivery measurement - FAD For the use of the FAD functionality the following prarameters have to be entered into the vortex flowmeter: • Ambient temperature (inlet) • Atmospheric pressure (inlet) •...
  • Page 84: Gross Heat Measurement

    OPERATION SITRANS FX330 6.8.2 Gross heat measurement In order to calculate gross power the mass flow (compensated by density) is multiplied by the specific enthalpy: Gross power [Q ] = mass flow [Q ] x enthalpy [H] When measuring gross heat, internally both the flow totalizer and the energy totalizer are used.
  • Page 85: Net Heat Measurement

    OPERATION SITRANS FX330 6.8.3 Net heat measurement To determine the amount of energy, which is consumed by a plant, the gross heat quantity must be reduced by the amount of energy, which is returned to the energy cycle. In the following...
  • Page 86: Status Messages And Diagnostic Information

    OPERATION SITRANS FX330 6.9 Status messages and diagnostic information The diagnostic messages are displayed in accordance with NAMUR standard NE 107. The error messages for the device are divided into status groups, each with one status signal. There are 16 status groups with fixed status signals and 8 groups with variable status signals.
  • Page 87 OPERATION SITRANS FX330 Status Event group Single event Description Actions to eliminate the type event Sensor Fatal Sensor Error An internal error in the Perform a hard reset. If the sensor module has occured. message recurs, contact the manufacturer. No Temperature Sensor...
  • Page 88 OPERATION SITRANS FX330 Status Event group Single event Description Actions to eliminate the type event Configuration Inconsistent NVRAM Inconsistent data in the Perform a hard reset. If the parameter memory message recurs, contact the manufacturer. Error Starting SIL Mode Error in starting SIL mode...
  • Page 89 OPERATION SITRANS FX330 Status Event group Single event Description Actions to eliminate the type event Sensor Flow Meas. Out of Spec. The vortex frequency or the Check the process volume flow is out of range. conditions. The real flow is higher or lower than the indicated value.
  • Page 90 OPERATION SITRANS FX330 Status Event group Single event Description Actions to eliminate the type event Configuration Incons. Converter Calib. Faulty calibration data in the Contact the manufacturer. converter module. Incons. Sensor Calibration Faulty calibration data in the sensor module SIL Verification Required SIL mode is requested.
  • Page 91: A12 Plausibility Checks

    OPERATION SITRANS FX330 6.10 A12 plausibility checks When configuring the device, a number of complex "cluster" checks are run internally on the proposed configuration in order to make sure it is valid. Thus when saving a configuration the device might raise an error like this: "Failed E01", which indicates an error cluster number.
  • Page 92: Service

    SERVICE SITRANS FX330 7.1 Replacing signal converter / LC display The signal converter has to be replaced by a converter of the same type. The item number 7 must match: 40021445xx Figure 7-1: Connect transmitter module 1 Connector for LC display...
  • Page 93: Maintaining The O-Rings

    SERVICE SITRANS FX330 7.2 Maintaining the O-rings Figure 7-2: Maintaining the O-rings 1 Display cover 2 Rear cover Whenever either the display cover 1 or the rear cover 2 of the housing is opened and closed again, make sure that the O-rings are well greased or being replaced if need be (O-ring 94x2,5- NBR-70K, ISO 3601-1).
  • Page 94: Spare Parts Availability

    For more precise information, please contact your local sales office. 7.5 Return procedure If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages. CAUTION!
  • Page 95: Disposal

    SERVICE SITRANS FX330 Required forms • Delivery note • Return goods delivery note (http://www.siemens.com/processinstrumentation/ returngoodsnote) with the following information: - Product (item description) - Number of returned devices/replacement parts - Reason for returning the item(s) • Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues.
  • Page 96: Technical Data

    TECHNICAL DATA SITRANS FX330 8.1 Functional principle Vortex flowmeters are used to measure the flow of gases, vapours and liquids at completely filled pipes. The measuring principle is based on the Karman vortex street. The measuring tube contains a bluff body at which vortex shedding occurs and which is detected by a sensor unit located behind.
  • Page 97: Technical Data

    TECHNICAL DATA SITRANS FX330 8.2 Technical data INFORMATION! • The following data is provided for general applications. If you require data that is more relevant to your specific application, please contact us or your local sales office. Additional information (certificates, special tools, software,...) and complete product •...
  • Page 98 TECHNICAL DATA SITRANS FX330 Measuring accuracy Reference condition Reference conditions Water at +20°C / +68°F Air at +20°C / +68°F and 1.013 bara / 14.7 psia Maximum measuring error ±0.75% of measured value (Re ≥ 20000) Volume flow (liquid) ±2.0% of measured value (10000 < Re < 20000) ±1.0% of measured value (Re ≥...
  • Page 99 TECHNICAL DATA SITRANS FX330 Other conditions Ingress protection Compact version: IP66/67 Remote version: signal converter housing: IP66/67; flow sensor housing: IP66/67 Installation conditions ≥ 15 x DN without disturbing flow, after pipe narrowing, after a single 90° bend Inlet section ≥...
  • Page 100 TECHNICAL DATA SITRANS FX330 Current output Type ® 4...20 mA HART (passive) Output data Volume flow, mass flow, norm. volume flow, gross/net power, free air delivery, density, temperature (internal sensor), pressure, vortex frequency, flow velocity Resolution 5 µA Linearity / accuracy 0.1% (of read value)
  • Page 101 TECHNICAL DATA SITRANS FX330 Pulse output Output data Volume, mass, norm. volume, gross/net energy Pulse rate Max. 1000 pulses/s Power supply Non-Ex: 24 VDC as NAMUR or open < 1 mA, maximum 36 V, closed 120 mA, U < 2 V Ex: 24 VDC as NAMUR or open <...
  • Page 102: Dimensions And Weights

    TECHNICAL DATA SITRANS FX330 8.3 Dimensions and weights 8.3.1 Flange versions a = 148.5 mm / 5.85" b = 85.8 mm / 3.38" Option: c = 171.5 mm / 6.76" Version with two signal converter Dimensions of flange version EN 1092-1 [mm]...
  • Page 103 TECHNICAL DATA SITRANS FX330 Nominal size Pressure rating 416.3 396.8 396.8 191.5 171.5 169.3 416.3 396.8 396.8 191.5 171.5 169.3 416.3 416.3 396.8 191.5 171.5 169.3 416.3 416.3 396.8 191.5 171.5 169.3 442.1 416.3 416.3 202.8 191.5 171.5 442.1 416.3 416.3...
  • Page 104 TECHNICAL DATA SITRANS FX330 Weight of flange version EN 1092-1 [kg] Nominal size Pressure with without F1R 1 with F1R 1 F2R 2 with F2R 2 rating without without Pressure sensor Pressure sensor Pressure sensor 10.8 10.2 14.8 14.2 13.3 12.7...
  • Page 105 TECHNICAL DATA SITRANS FX330 Dimensions of flange version ASME B16.5 a = 148.5 mm / 5.85" b = 85.8 mm / 3.38" c = 171.5 mm / 6.76" Dimensions of flange version ASME B16.5 [mm] Nominal size Pressure rating Class ½...
  • Page 106 TECHNICAL DATA SITRANS FX330 Nominal size Pressure rating Class 442.1 416.3 396.8 202.8 191.5 171.5 442.1 416.3 396.8 202.8 191.5 171.5 468.8 442.1 416.3 229.5 202.8 191.5 468.8 442.1 416.3 229.5 202.8 191.5 492.8 468.8 442.1 255.0 229.5 202.8 492.8 468.8...
  • Page 107 TECHNICAL DATA SITRANS FX330 Dimensions of flange version ASME B16.5 [inch] a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Dimensions of flange version ASME B16.5 [inch] Nominal size Pressure rating Class ½...
  • Page 108 TECHNICAL DATA SITRANS FX330 Nominal size Pressure rating Class 17.4 16.4 15.6 7.54 6.76 17.4 16.4 15.6 7.54 6.76 18.5 17.4 16.4 9.04 7.54 18.5 17.4 16.4 9.04 7.54 19.4 18.5 17.4 10.0 9.04 19.4 18.5 17.4 10.0 9.04 1 F1R - single reduction 2 F2R - double reduction Weight of flange version ASME B16.5 [lb]...
  • Page 109: Sandwich Version

    TECHNICAL DATA SITRANS FX330 8.3.2 Sandwich version a = 133 mm / 5.24" b = 105 mm / 4.13" Dimension H x 2 c = 179 mm / 7.05" Specified weight: + 2.8 kg / 6.2 lb Sandwich version EN...
  • Page 110 TECHNICAL DATA SITRANS FX330 a = 135 mm / 5.32" b = 108 mm / 4.26" c = 184 mm / 7.25" Sandwich version ASME Nominal size Pressure Dimensions [inch] Weight [lb] rating Class with without Pressure sensor ½ 0.63 1.77...
  • Page 111: Dimensions Of Remote Version

    TECHNICAL DATA SITRANS FX330 8.3.3 Dimensions of remote version Dimension a a a a Flange & sandwich version Flange version ½ 1½ [mm] 315.7 315.2 319.2 235.2 337.2 353.7 373.2 398.9 425.7 449.7 ["] 12.5 12.4 12.6 12.8 13.3 14.0 14.7...
  • Page 112: Flow Tables

    TECHNICAL DATA SITRANS FX330 8.4 Flow tables Measuring ranges Nominal size DN - EN 1092-1 NPS - ASME B16.5 [gph] Water 0.36 5.07 95.61 1339 0.81 11.40 3012 1½ 2.04 28.58 7550 3.53 49.48 13072 7.74 108.3 2045 28632 13.30 186.2...
  • Page 113 TECHNICAL DATA SITRANS FX330 Measuring range saturated steam: 1...7 barg Gauge pressure [barg] Density [kg/m³] 1.134 2.419 3.272 4.166 Temperature [°C] 120.4 148.0 160.2 170.5 Flow rate [kg/h] [kg/h] [kg/h] [kg/h] ASME 1092-1 B16.5 5.07 36.94 7.41 78.8 8.62 106.6 9.73...
  • Page 114 TECHNICAL DATA SITRANS FX330 Measuring range saturated steam: 15...100 psig Gauge pressure [psig] Density [lb/ft³] 0.0721 0.1496 0.2033 0.2564 Temperature [°F] 249.8 297.7 320.0 337.8 Flow rate [lb/h] [lb/h] [lb/h] [lb/h] [lb/h] ASME 1092-1 B16.5 11.09 81.44 16.42 173.7 19.05 235.0...
  • Page 115: Notes

    NOTES SITRANS FX330 05/2016 - A5E36751269-AA www.siemens.com/flow...
  • Page 116 For more information www.siemens.com/flow Siemens A/S Subject to change without prior notice Flow Instruments Order No.: A5E36751269 Coriolisvej 1-3 Lit. No.: A5E36751269-AA DK-6400 Soenderborg © Siemens AG 05.2016 A5E36751269 www.siemens.com/processautomation...

This manual is also suitable for:

Sitrans fxt030

Table of Contents