Mitsubishi Electric Lossnay LGH-15RX3 Technical Manual page 99

Table of Contents

Advertisement

CHAPTER 7 G Installation Considerations
4.3 Combination dimensions
G
The combined-type uses a combination of single-type units.
G
The combined-type is shipped in the disassembled state. (A combination of single-type units.)
LUT-2302
LUT-2303
1000
1500
LUT-3002
LUT-3003
1000
1500
4.4 Maintenance space
G
The Lossnay Core is cleaned from the intake/exhaust chamber
sides.
Allow an inspection space of 50 cm or more in the chamber.
G
Ensure that the Core inspection door can open and close, and
always install an inspection door for cleaning the ducts.
4.5 Transportation and installation
G
Always use shackles to lift the Lossnay Core section as shown in the figure. Fix the main unit with the eyenuts for lifting the
unit, and suspend the unit in four places. (Fig. 1)
G
Adjust the rope length so that the angle between the rope and the unit is 45° or more. (Fig. 1)
G
The panel will be damaged if the rope directly contacts the unit.
G
When combining the units, use the enclosed top connection fittings (two) and bottom connection fittings (two). Securely fix
the top with the four M10 screws and four washers and the bottom with eight M8 screws so that the fitting with the flange is
tight.
G
Always leave the maintenance space shown in the diagram.
G
The foundation for the unit must be sturdy and level.
G
Install the unit perpendicularly to the foundation and securely fix the unit with anchor bolts.
G
Install the unit so rain water will not enter the unit from the ducts.
96
LUT-2304
LUT-2305
2000
2500
LUT-3004
LUT-3005
2000
2500
LUT-2306
LUT-2307
3000
3500
LUT-3006
LUT-3007
3000
3500
Lossnay core
SA
Air
conditioner
LUT-2308
4000
LUT-3008
4000
Unit (mm)
Door
Maintenance space 500 or more
RA
Filter
Lossnay
Inspection door
OA
EA
Exhaust fan
Unit (mm)