The Lossnay uses the forced simultaneous supply/exhaust method so the
insufficient ventilation found in standard ventilators with no air intake is
not found.
Caution
(1) The fresh air supplied to the room should not short circulate being
drawn back into the return grille. It should flow through the entire
room.
(2) The relation of the supply and suction flows of the air conditioner must
be also considered.
Supply grille
Air
conditioner
I The air intake/exhaust grille on the outer wall is in the open and so
there is a natural wind, with the result that short circulation will not
occur easily. However, if the wind blows from the exhaust grille
towards the intake grille, short circulation may occur, so these should
be placed as far apart as possible.
The guideline for the distance is three times the duct diameter.
Duct diameter
ø100
300
ø150
450
ø200
600
ø250
750
Several units can be operated with the optional control switch.
Refer to "Chapter 3 Performance comparisons with various heat recovery
units and ventilators".
For the ceiling embedded-type, the unit is installed in the false ceiling, so
an inspection hole is required at the Core and filter removal section and
fan maintenance section.
Refer to the catalog for details.
Periodic inspection and cleaning of the Lossnay Core and air filter is
necessary. Refer to "Chapter 9 Maintenance" for details.