CHAPTER 7 G Installation Considerations
3.4 Transportation and installation
(1) LP-200B · 350B · 500B
G
The product is shipped in the fully assembled state.
Transport the unit gently and do not apply shock or tilt the
unit.
G
Use eyebolts (or eyenuts) when lifting the unit. Always use
the four eyebolts, and fix with rope. Adjust the rope length
so that the angle between the rope and the unit is 45° or
more.
The panel will be damaged if the rope directly contacts the
unit. Always use filler plates or wood.
G
The foundation for the unit must be sturdy and level.
G
Install the unit perpendicularly to the foundation and
securely fix the unit with anchor bolts.
G
Install the unit where it will not come into contact with rain
water, and where rain water will not enter the unit from the
ducts.
G
The unit may be disassembled into two par ts, and
transported with the following procedure if installation as a
complete product is not possible.
Disassembly
1) Remove the cover for the air filter and Lossnay Core.
Remove the air filter and then the Lossnay Core.
2) Disconnect the cord (for bypass) connected to the fan
chamber motor in the lower part of the unit.
3) Remove the six screws fixing the top and bottom of the unit.
(2) LP-750B · 1000B
G
This product is shipped in two parts and assembled at the
installation site.
G
Always lift the Core chamber and the fan chamber
separately even when lifting the entire product in the
assembled state using the eyebolts (or eyenuts) mounted
on the unit.
G
Always be sure to use the eyebolts (or eyenuts) when lifting
the unit. Always use the four eyebolts, and securely fix the
rope. Adjust the rope length so that the angle between the
rope and the unit is 45° or more.
G
The foundation for the unit must be sturdy and level.
G
Install the unit perpendicularly to the foundation and
securely fix the unit with anchor bolts.
G
Install the unit so rain water will not enter the unit from the
ducts.
G
To assemble the separate parts, align the slots on the core
chamber to the bolts on top of the fan chamber, and fix with
the enclosed washers and nuts (six each).
G
Remove the inspection hole cover and connect the geared
motor plug for the bypass to the plug in the Core chamber
from inside.
94
Filler plate
Weight when disassembled
Top
(Core
chamber)
LP-200B
140
LP-350B
230
LP-500B
300
Weight when disassembled
Top
(Core
chamber)
LP-750B
140
LP-1000B
230
Hook for
suspension
Unit (kg)
Bottom
(fan
Total
chamber)
240
380
290
520
380
680
Screw
Washer
Cord (for by-pass)
Unit (kg)
Bottom
(fan
Total
chamber)
240
380
290
520