6.4 Transportation and installation
The product is shipped in the fully assembled state. Transport the unit gently and do not apply shock.
When installing, allow a slight slant so that the drain pipe is lower than the unit.
1) Use eyebolts (or eyenuts) and rope when lifting the unit. Make sure that the rope can withstand the weight of the unit.
Always use all four eyebolts (or eyenuts), and fix the rope.
Adjust the rope length so that the angle between the rope and the unit is 45° or more.
Caution
G
Use filler plates to protect the panel so that the panel is not damaged by the rope during lifting.
G
The unit will be damaged if the rope directly contacts the unit.
G
Confirm that the drain pipe is at the set position when installing.
G
The foundation must withstand the weight of the unit.
G
Securely fix the unit with anchor bolts, etc.
G
Make sure that rain water will not enter the unit from the ducts.
G
Make sure that the indoor-type does not come into contact with rain water.
G
Make sure that air will not leak and water will not enter from the duct connections.
A
B
1730
1170
2600
2040
3470
2910
4340
3780
Pitch
ø10 hole
100 × 8 = 800
890
930
Flange details
Lossnay core
Air filter can be
installed (optional)
ø16
Core, air filter
ø34
removal cover
Duct connection flange
Drain pipe details
Main unit
CHAPTER 7 G Installation Considerations
C
1250
2120
2990
3860
High temperature,
Highly humid air A
Low temperature,
low humid air A
50
100
850
200
50
50
860
2100
960
Drain pipe
(Detailed diagram)
Rope
Reinforcement material
Eye nut
Horizontal
flange
Drain
pipe
D
Pitch 100 × 10 = 1000
1210
Pitch 100 × 20 = 2000
2080
Pitch 100 × 27 = 2700
2950
Pitch 100 × 36 = 3600
3820
B'
Eye nut M16
A'
850
100
Unit (mm)
E
Unit (mm)
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents