CHAPTER 7 G Installation Considerations
3. Building Lossnay Pack-type (LP-200B · 350B · 500B · 750B · 1000B)
System concept diagram
Package air conditioner
LP-200B
Air handling unit
LP-1000B
(1) The LP-200B · 350B · 500B · 750B and 1000B building Lossnay Packs models are available with an air volume of 1000 to
3
13000 m
/h.
(2) Select an adequate model according to the building size, air volume for application and static pressure of outside unit.
Air passage
Exhaust side tilter
By-pass damper
RA
(Return air)
High efficiency
filter unit
(optional)
Supply fan
SA
(Supply air)
1. The fresh outdoor air is filtered with the intake filter,
and the heat is recovered with the Lossnay Core
(during winter; heated and humidified, during summer;
cooled and dehumidified). Then it is supplied by the
supply fan.
2. The optional high efficiency filter is placed between the
Lossnay Core and supply fan, to refilter the air that has
been filtered by the intake filter.
3. The stale air passes through the damper, and is filtered
by the exhaust filter. The heat is recovered with the
Lossnay Core, and then discharged by the exhaust fan.
4. The bypass passage for normal ventilation bypasses
the air on the exhaust side. If the bypass damper is
closed, the stale air will be directly drawn in by the
exhaust fan and discharged.
92
Installation examples
<Combination with air handling unit>
RA
OA
EA
Lossnay
Chamber
Air handling unit
LP-350B
3.1 Main unit base installation
Lossnay core
Supply air filter
OA
(Outdoor
air)
Exhaust fan
EA
(Exhaust
air)
3.2 Maintenance space
<Combination with package air
conditioner>
SA
OA
EA
Lossnay
LP-350B
surface diagram
50
50
A
A
B
800
Maintenance
space for
core
air filter
and air-
supply
fan
Switch box
RA
SA
Chamber
Package air
conditioner
6 - ø20 holes
Unit (mm)
Model
A
B
C
D
LP-200B
500 1230 950 1000
LP-350B
700 1560 1120 1170
LP-500B
950 2070 1230 1280
LP-750B
950 2070 1230 1280
LP-1000B 950 2070 1350 1400