11. Vertical Installation of LGH Series
Installation of ceiling embedded-type industrial Lossnay
11.1 Top/bottom reverse installation
All LGH-RX
models can be installed in reverse.
3
11.2 Vertical installation
Vertical installation is possible, but the installation pattern is limited for some models. Refer to the following table for the
installation patterns.
Model name
LGH-15RX
3
LGH-25RX
3
LGH-35RX
3
LGH-50RX
3
LGH-80RX
3
LGH-100RX
3
(Precautions)
G
When constructing for vertical installation, make sure that rain water will not enter the Lossnay unit from outdoors.
G
Always transport the unit in the specified state. Vertical installation applies only to after installation, and does not apply to
transportation.
(The motor may be damaged if the unit is transported vertically.)
11.3 Slanted installation
Slanted installation is not possible.
Special note
The LGH-RX
model was conventionally designed for being embedded in the ceiling. If possible, vertical installation should be
3
avoided in regard to construction and maintenance.