"In" - Information Menu
12 views of information are available.
Press the Heating buttons to scroll the list of information in increasing or decreasing order. Press the DHW buttons to
display the value.
Contents
Description
t01
NTC Heating sensor (°C)
t02
NTC Return sensor (°C)
t03
NTC DHW sensor (°C)
t04
NTC (optional) External sensor (°C)
t05
NTC Flue gas sensor (°C)
F06
Actual fan rpm
L07
Actual burner power (%)
F08
Actual DHW flow rate (l/min/10)
P09
Actual system water pressure (bar/10)
P10
Actual modulating pump speed (%)
P11
Burner operating hours
F12
Flame status
Notes:
1. In case of damaged sensor, the PCB displays hyphens (- -).
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the PCB Service
Menu, or exiting occurs automatically after 15 minutes.

"Hi" - History Menu

The PCB can store the last 8 fault codes: the History data item H1 represents the most recent fault that occurred, where-
as the History data item H08 represents the least recent.
(The fault codes can also be viewed in the relevant menu of the optional OpenTherm Remote Timer Control).
Press the Heating (+) button to scroll through the list of faults in increasing order or (-) button to view in decreasing order.
Press the DHW (+) button to display the fault value.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the PCB Service
Menu, or exiting occurs automatically after 15 minutes.

"rE" - History Reset

Press the Winter/Summer/Off-On button for 3 seconds to delete all stored faults in the History Menu: NOTE the PCB
automatically exits the Service Menu, in order to confirm the operation.
Press the Reset button for 10 seconds to exit the PCB Service Menu, or exiting occurs automatically after 15 minutes.
EN
Range
0÷125 °C
0÷125 °C
0÷125 °C
+70 ÷ -30°C (negative values flash)
0÷125 °C
00÷120 x100RPM
00%=Min., 100%=Max.
00÷99 l/min/10
00=With Pressure switch open,
14=With Pressure switch open, 00-99 bar/10 with Pressure transducer
00÷100%
00÷99 x 100 hours
00÷255 μA