User Load Curve - ABB ACQ810 Firmware Manual

Standard pump control program for drives
Hide thumbs Also See for ACQ810:
Table of Contents

Advertisement

No.
Name/Value
Process act
Proc PID out
Pointer
33.11
Superv3 hi
-32768.00 ...
32768.00
33.12
Superv3 lo
-32768.00 ...
32768.00
34

34 User load curve

34.01
Overload func
Bit
Function
Ena sup (Enable supervision)
0
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
Input value sel (Input value selection)
1
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
Ena warn (Enable warning)
2
0 = Disabled
1 = Enabled: Drive generates alarm
Ena fault (Enable fault)
3
0 = Disabled
1 = Enabled: Drive trips on fault
Ena lim integ (Enable limit integration)
0 = Disabled
4
1 = Enabled: Integration time defined by parameter
the supervision is evoked, the current or torque is limited by the upper boundary of the
load curve.
Ena lim always (Enable limit always)
0 = Disabled
5
1 = Enabled: The current or torque is always limited by the upper boundary of the load
curve.
Description
04.01 Act val
(see page 123).
04.05 Process PID out
(see page 123).
Value pointer setting (see
109).
Selects the upper limit for supervision 3. See parameter
33.09 Superv3
func.
Upper limit for supervision 3.
Selects the lower limit for supervision 3. See parameter
33.09 Superv3
func.
Lower limit for supervision 3.
Configuration of user load curve.
See also section
User-definable load curve
Configures the supervision of the upper boundary of the user
load curve.
LCURVE (0x2312)
LOAD CURVE (0x2312)
Terms and abbreviations
on page 71.
when the curve is exceeded.
when the curve is exceeded.
34.18 Load integ time
Parameters 205
FbEq
1073742849
1073742853
on page
-
100 = 1
100 = 1
is used. After

Advertisement

Table of Contents
loading

Table of Contents