192 Parameters
No.
Name/Value
28.03
Act val 2 src
Zero
AI1 scaled
AI2 scaled
AI3 scaled
AI4 scaled
AI5 scaled
FBA procact
Shared sig1
Flow act
Pointer
28.04
Act val func
Act1
Add
Sub
Mul
Div
Max
Min
Sqrt sub
Sqrt add
28.05
Act max val
0.00 ... 32768.00%
28.06
Act unit sel
%
m3/h
bar
kPa
GPM
psi
inHg
mbar
Pa
inH2O
in wg
ft wg
Description
Selects the source of process actual value 2.
No source selected.
02.05 AI1 scaled
(see page 113).
02.07 AI2 scaled
(see page 113).
02.09 AI3 scaled
(see page 113).
02.11 AI4 scaled
(see page 114).
02.13 AI5 scaled
(see page 114).
02.41 FBA act val
(see page 122).
02.43 Shared signal 1
(see page 122).
05.05 Flow act
(see page 125).
Value pointer setting (see
109).
Defines how the final process actual value is calculated from
the two sources selected by parameters
and
28.03 Act val 2
src.
The actual value is determined by parameter
1/2
sel.
Sum of actual value 1 and actual value 2.
Actual value 2 subtracted from actual value 1.
Actual value 1 multiplied by actual value 2.
Actual value 1 divided by actual value 2.
Greater of the two actual values used.
Smaller of the two actual values used.
Square root of (actual value 1 – actual value 2).
Square root of actual value 1 + square root of actual value 2. 8
Actual value scaling. The setting equals 100% of process
setpoint and is typically set to the value that corresponds to
the top end of the sensor range.
Actual value scaling.
Defines the unit for both process actual value and process
setpoint. Typically the measured quantity is selected.
%
3
m
/h
bar
kPa
GPM
psi
inHg
mbar
Pa
inH
O
2
in wg
ft wg
Terms and abbreviations
28.02 Act val 1 src
28.01 Act val
FbEq
0
1073742341
1073742343
1073742345
1073742347
1073742349
1073742377
1073742379
1073743109
on page
-
0
1
2
3
4
5
6
7
100 = 1%
4
20
22
23
24
25
29
44
45
58
59
60

Advertisement

Table of Contents
loading

Table of Contents