Drive Status - ABB ACQ810 Firmware Manual

Standard pump control program for drives
Hide thumbs Also See for ACQ810:
Table of Contents

Advertisement

126 Parameters
No.
Name/Value
05.35
kWh December
05.36
First in order
05.37
Time autochg
05.39
Next start node
06

06 Drive status

06.01
Status word1
Bit
Name
0
Ready
1
Enabled
2
Started
3
Running
4
Em off
(off2)
5
Em stop
(off3)
6
Ack startinh 1 = Start inhibit is active.
7
Alarm
8
Ext2 act
9
Local fb
10
Fault
11
Local panel 1 = Local control is active, ie. drive is controlled from PC tool or control
12
Fault(-1)
13...15 Reserved
Description
Energy consumed during last December.
The first pump in the current Autochange sequence.
Time elapsed since last Autochange.
(Only valid when the drive is master.) Node number of the
next drive to be started.
Drive status words.
Status word 1 of the drive.
Information
1 = Drive is ready to receive start command.
0 = Drive is not ready.
1 = External run enable signal is received.
0 = No external run enable signal is received.
1 = Drive has received start command.
0 = Drive has not received start command.
1 = Drive is modulating.
0 = Drive is not modulating.
1 = Emergency OFF2 is active.
0 = Emergency OFF2 is inactive.
1 = Emergency OFF3 (ramp stop) is active.
0 = Emergency OFF3 is inactive.
0 = Start inhibit is inactive.
1 = Alarm is active. See chapter
0 = No alarm is active.
1 = External control EXT2 is active.
0 = External control EXT1 is active.
1 = Fieldbus local control is active.
0 = Fieldbus local control is inactive.
1 = Fault is active. See chapter
0 = No fault is active.
panel.
0 = Local control is inactive.
1 = No fault is active.
0 = Fault is active. See chapter
Fault
tracing.
Fault
tracing.
Fault
tracing.
FbEq
1 = 1 kWh
1 = 1
1 = 1 ms
1 = 1
-