Set-Up Procedure - IntesisBox IBBACMEB0100000 User Manual

Bacnet server, m-bus meters
Table of Contents

Advertisement

BACnet Server – M-Bus
®
IntesisBox

Set-up procedure

1. Install IntesisBox MAPS on your laptop, use the setup program supplied for this and follow the instructions given
by the Installation wizard.
2. Install IntesisBox in the desired installation site. Installation can be on DIN rail or on a stable not vibrating surface
(DIN rail mounted inside a metallic industrial cabinet connected to ground is recommended).
3. If using BACnet IP, connect the communication cable coming from the BACnet IP network to the port marked as
Ethernet on IntesisBox (More details in section 0).
If using BACnet MSTP, connect the communication cables coming from the BACnet MSTP network to the port
marked as Port A on IntesisBox (More details in section 0).
4. Connect the M-Bus communication cable coming from the M-Bus network to the port marked as Port A on
IntesisBox (More details in section 0).
5. Power up IntesisBox. The supply voltage can be 9 to 30 Vdc or just 24 Vac. Take care of the polarity of the supply
voltage applied.
WARNING! In order to avoid earth loops that can damage IntesisBox and/or any other equipment connected
to it, we strongly recommend:
The use of DC power supplies, floating or with the negative terminal connected to earth. Never use a
DC power supply with the positive terminal connected to earth.
The use of AC power supplies only if they are floating and not powering any other device.
6. If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as USB of
IntesisBox (More details in section 0).
If you want to connect using IP, connect the Ethernet cable from the laptop PC to the port marked as USB of
IntesisBox (More details in section 0).
7. Open IntesisBox MAPS, create a new project selecting a copy of the one named IBOX-BAC-MBUS.
8. Modify the configuration as desired, save it and download the configuration file to IntesisBox as explained in the
IntesisBox MAPS user manual.
9. Visit the Diagnostic section and check that there is communication activity, some TX frames and some other RX
frames. This means that the communication with the BACnet master device and Modbus Slave devices is OK.
In case there is no communication activity between IntesisBox and the BACnet and/or Modbus devices, check
that those are operative: check the baud rate, the communication cable used to connect all devices and any
other communication parameter.
© Intesis Software S.L.U. - All rights reserved
IntesisBox is a registered trademark of Intesis Software SLU
User Manual r1.0 eng
URL
http://www.intesisbox.com
email
info@intesisbox.com
tel
+34 938047134
39/41

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IBBACMEB0100000 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Ibbacmeb0200000Ibbacmeb0600000Ibbacmeb1200000

Table of Contents