BACnet Server – M-Bus
®
IntesisBox
Connection to M-Bus
The gateway connects to the M-Bus system directly withour requiring any external RS232 or RS485 to M-Bus level
converter.
Connect the M-Bus bus to connectors A3 (+) and A4 (-) of gateway's PortA.
Remember that the IntesisBox provides 36VDC M-Bus voltage to the bus, acting as a M-Bus level converter as well.
In case there is no response from the M-Bus device(s) to the frames sent by IntesisBox, check that they are operative
and reachable from the network connection used by IntesisBox. You can use an EIA-485-to-USB converter and a M-
Bus Master software (such as MBSheet or similar) to double check the M-Bus installation.
Connection to the configuration tool
This action allows the user to have access to configuration and monitoring of the device (more information can be
found in the configuration tool User Manual). Two methods to connect to the PC can be used:
•
Ethernet: Using the Ethernet port of IntesisBox.
•
USB: Using the console port of IntesisBox, connect a USB cable from the console port to the PC.
© Intesis Software S.L.U. - All rights reserved
IntesisBox is a registered trademark of Intesis Software SLU
User Manual r1.0 eng
URL
http://www.intesisbox.com
email
info@intesisbox.com
tel
+34 938047134
34/41
Need help?
Do you have a question about the IBBACMEB0100000 and is the answer not in the manual?
Questions and answers