Network Status (Net) Indicator; Module Status (Ok) Indicator - Allen-Bradley SoftLogix 5800 User Manual

Table of Contents

Advertisement

Appendix F
Status Indicators
260

Network Status (NET) Indicator

NET Indicator
Display
Solid green
CIP connections
established
Flashing green
No CIP connections
established
Flashing red
Lost network
connection

Module Status (OK) Indicator

OK Indicator
Display
Solid green
OK
Flashing green
Standby
Solid red
Major fault
Flashing red
Minor fault
Rockwell Automation Publication 1789-UM002K-EN-P - January 2015
Description
• The module has an IP address and CIP connections (Class 1 or
Class 3) are established.
• Normal operation. No action required.
• The module has an IP address, but no CIP connections are
established.
• Normal operation if no connections are configured. No action
required.
• If connections are configured, check connection originator for
connection error code.
• The module detected that the network connection has been
lost.
• Verify that all Ethernet cables are connected.
• Verify that the Ethernet switch is powered.
Description
• The module is operating correctly.
• Normal operation. No action required.
• The module is not configured correctly.
• Verify the module's configuration.
• An unrecoverable fault has occurred.
• Cycle power to the controller. Correct the fault.
A recoverable fault has occurred. Correct the fault.