Add, Configure, Monitor, and Replace CIP Safety I/O Devices
Replace a Device by Using the
Logix Designer Application
90
You can use the Logix Designer application to replace a safety I/O device on an
Ethernet network. To replace a Guard I/O module on a DeviceNet network,
your choice depends on the type of module.
Table 28 - Software
If you are using a
1791DS Guard I/O module with 1756-DNB
adapter
1734 POINT Guard I/O module with a
1734-PDN adapter
If you are relying on a portion of the CIP Safety system to maintain SIL 3
behavior during device replacement and functional testing, the Configure
Always feature cannot be used. Go to
When No Safety Signature Exists' Enabled on page
If the entire routable CIP Safety control system is not being relied on to
maintain SIL 3/PLe during the replacement and functional testing of a device,
the Configure Always feature can be used. Go to
Always' Enabled on page
Safety I/O device replacement is configured on the Safety tab of the
GuardLogix controller.
Figure 23 - Safety I/O Device Replacement
Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Use
The Logix Designer application Below
RSNetWorx™ for DeviceNet
software
Replacement with 'Configure Only
Replacement with 'Configure
96.
See
Replace a POINT Guard I/O Module
by Using RSNetWorx for DeviceNet
Software on page 97