Table 40 - Connect to the Controller
If the software indicates
Unable to connect to controller. Mismatch between the
offline project and the controller serial number. Selected
controller may be the wrong controller.
Unable to connect to controller. The revision of the offline
project and the controller's firmware are not compatible.
You need to upload or download to go online by using the
open project.
Unable to connect in a manner that preserves safety task
signature. Controller's firmware minor revision is not
compatible with safety task signature in offline project.
Unable to connect to controller. Incompatible safety task
signature cannot be deleted while project is safety-locked.
3. Follow the directions in the table below to connect to the controller.
Then
Connect to the correct controller, select another project file, or choose the Update project serial number checkbox
and choose Go Online... to connect to the controller and update the offline project serial number to match the
controller.
Choose one of the following options:
• Choose Update Firmware. Choose the required revision and click Update. Click Yes to confirm your selection.
IMPORTANT: The online project is deleted.
• To preserve the online project, cancel the online process and install a version of the Studio 5000 environment
that is compatible with the firmware revision of your controller.
Choose one of the following options:
• Upload to update the offline project.
• Download to update the controller project.
• Choose File to select another offline project.
• To preserve the safety task signature when the firmware minor revision is incompatible, update the firmware
revision in the controller to exactly match the offline project. Then go online to the controller.
• To proceed with the download despite the safety task signature incompatibility, click Download. The safety task
signature is deleted.
IMPORTANT: The safety system requires revalidation.
Cancel the online process. You must safety-unlock the offline project before attempting to go online.
When the controller and the Logix Designer application are online, the safety-
locked status and safety task signature of the controller match the controller's
project. The safety-lock status and safety task signature of the offline project
are overwritten by the controller. If you do not want the changes to the offline
project to be permanent, do not save the project file following the go online
process.
Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
Go Online with the Controller
Chapter 7
133