Blown Fuse Indicator & Trip
All bolted EJ-2 type fuses have inherent blown fuse in
dication because the striker pin at the top of the fuse
protrudes out when the fuse is blown. In the CR194
two-high, the striker pin drives the blown fuse indica
tor and trip bar which operates the blown fuse trip
(BFT) contact block. Tke BFT con tact block can be
wired to trip the controller off line to preven t single
phasing of the connected load (anti-single phase pro
tection ) . It can also be wired to an optional blown fuse
indicator mounted on the low-voltage door. Figure 1 4
shows the top of the bolted power fuse assembly with
the center blown fuse indicator in the "blown" posi
tion and the two outside blown fuse indicators in the
"normal" position. Figure 1 5 shows the BFT contact
block, with wiring removed for clarity.
-
Figure
14.
Blown fuse indicators with center phase indicating
"blown" and outside phases indicating "normal"
CR194 Two-High Vacuum Limitamp® Control
Figure 15. Blown fuse trip (BfT) contact block
with wiring removed for clarity
(