Martindale ET4000 / ET4500
Continuity measurement procedure
Select
R
LOWΩ
Set sub-function to (r1, rN, r2, R1+R2,
Enable and set the limit (optional).
Connect the test leads to the instrument.
Null the test lead resistance if required (see section 5.3.4 Nulling of test lead
resistance).
Disconnect the installation to be tested from the mains supply.
Connect the test leads to the installation wiring to be tested (see Figure 5.10 and
Figure 5.11: ).
Press the TEST key to perform the measurement.
After the measurement has finished store the result, if required, by pressing the
MEM key (ET4500 only).
Displayed result:
R.............. continuity resistance
R+ ........... result for positive test polarity
R- ............ result for negative test polarity
5.3.2 R LOWΩ, 200 mA resistance measurement
The resistance measurement is performed with automatic polarity reversal of the test
voltage.
R LOWΩ measurement procedure
Select
R
LOWΩ
Set sub-function to
Enable and set the limit (optional).
Connect the test leads to the instrument.
Null the test lead resistance if required (see section 5.3.4 Nulling of test lead
resistance).
Disconnect from the mains supply and discharge the installation to be tested.
Connect the test leads to the PE wiring to be tested.
Press the TEST key to perform the measurement.
After the measurement has finished store the result, if required, by pressing the
MEM key (ET4500 only).
function using the function selector switch.
Figure 5.12: Example of continuity result
function using the function selector switch.
R LOWΩ
with UP / DOWN keys.
R2
or R1+RN) with UP / DOWN keys.
35