MARTINDALE ET4000 Instruction Manual page 49

Multifunction installation testers
Table of Contents

Advertisement

Martindale ET4000 / ET4500
5.6.1 Line impedance and prospective short circuit current
Circuits for measurement of line impedance
Figure 5.30: Phase-neutral or phase-phase line impedance measurement
Line impedance measurement procedure
Select the
Z LINE
Set sub-function to
Select test parameters (optional).
Connect the test leads to the instrument.
Connect the test leads to the installation wiring to be tested (see Figure 5.30).
Press the TEST key to perform the measurement.
Store the result, if required, by pressing the MEM key (ET4500 only).
Figure 5.31: Examples of line impedance measurement result
Displayed results:
Z .............. line impedance
Isc ........... prospective short-circuit current
Lim .......... upper limit line impedance value
Prospective fault current I
where:
Un ........................ Nominal U
Scaling factor ....... Impedance correction factor (see chapter 4.4.4 Z factor).
function using the function selector switch.
Zline
using UP / DOWN keys.
is calculated from the measured impedance as follows:
PFC
I
PFC
Z
scaling
L
N
(
L
)
or U
voltage (see table below),
L-N
L1-L2
49
U
N
_
factor
Measurements