Figure 5.22: Trip-out current measurement result example
Displayed results:
I ........... trip-out current
Uci ....... contact voltage at trip-out current I or the end value when the RCD does
not trip
t ........... trip-out time
Testing considerations
Parameters set in one function are also kept for other RCD functions.
The measurement of contact voltage does not normally trip an RCD. However,
the trip limit of the RCD may be exceeded as a result of leakage current flowing
to the PE protective conductor or a capacitive connection between the L and PE
conductors.
RCD trip-out time and RCD trip-out current measurements will only be performed
if the contact voltage in the pre-test at nominal differential current is lower than
the set contact voltage limit.
Ulim can be selected in the Uc sub-function only.
Selective (time-delayed) RCDs have delayed response characteristics. As the
contact voltage pre-test or other RCD tests influence time delayed RCD's it takes
some time to return to normal state. Therefore a time delay of 30 s is inserted
before performing a trip-out test by default.
42