MARTINDALE ET4000 Instruction Manual page 51

Multifunction installation testers
Table of Contents

Advertisement

Martindale ET4000 / ET4500
Step 2: Measuring the voltage drop
Set sub-function to
Select test parameters (Fuse type must be selected).
Connect the test leads to the instrument.
Connect the test leads to the point in the wiring or socket to be tested (see Step
2 of Figure 5.33).
Press the TEST key to perform the measurement.
Store the result, if required, by pressing the MEM key (ET4500 only).
Step 1 - Zref
Figure 5.33: Examples of voltage drop measurement result
Displayed results:
ΔU ........... voltage drop
Isc ........... prospective short-circuit current
Z .............. line impedance at measured point
Zref ......... reference impedance
Voltage drop is calculated as follows:
where:
ΔU ........ calculated voltage drop
Z .......... impedance at test point
Z
...... impedance at reference point
REF
I
.......... rated current of selected fuse
N
U
........ nominal voltage (see table below)
N
Testing considerations
If the reference impedance is not set the value of Z
The Z
is cleared (set to 0.00 Ω) by pressing the NULL key while the instrument
REF
is not connected to a voltage source.
ΔU
using UP / DOWN keys.
(
Z
 
U
%
U
Input voltage range (L-N or L1-L2)
n
(93 V  U
110 V
230 V
(185 V  U
(321 V  U
400 V
Step 2 - Voltage drop
Z
)
I
REF
N
100
U
N
 134 V)
L-N
 266 V)
L-N
 485 V)
L-L
REF
51
Measurements
is considered as 0.00 Ω.