Martindale ET4000 / ET4500
Voltage measurement procedure
Select the
VOLTAGE TRMS
Connect the test leads to the instrument.
Connect the test leads to the wiring or socket to be tested (see Figure 5.2 and
Figure 5.3).
Store voltage measurement results, if required, by pressing the MEM key
(ET4500 only).
Measurement starts immediately after selection of the
Figure 5.4: Examples of voltage measurement in a three-phase system
Displayed results for a single phase system:
Uln .......... voltage between phase and neutral conductors
Ulpe ........ voltage between phase and protective conductors
Unpe ....... voltage between neutral and protective conductors
f ............... frequency
Displayed results for a three-phase system:
U12 .......... voltage between phases L1 and L2
U13 .......... voltage between phases L1 and L3
U23 .......... voltage between phases L2 and L3
1.2.3 ........ correct connection – clockwise rotation sequence
3.2.1 ........ incorrect connection – anticlockwise rotation sequence
f ............... frequency
Testing considerations
When only two of the three test terminals are connected to the electrical
installation under test, only the voltage indication between those two terminals is
correct.
function using the function selector switch.
VOLTAGE TRMS
29
Measurements
function.