Platinum resistance thermometer
The following table lists the types of platinum resistance thermometers that can be used with the temperature control module
and the temperature measuring range.
Platinum resistance
thermometer type
Temperature measuring
range
Pt100
-200.0 to 600.0
-200.0 to 200.0
-200.0 to 850.0
JPt100
-200.0 to 500.0
-200.0 to 200.0
-200.0 to 640.0
For the R60TCTRT2TT2 and R60TCTRT2TT2BW, only CH1 and CH2 can be used.
2.2 Type of Temperature Sensors, Temperature Measuring Range, Resolution, and Effect from Wiring Resistance
Resolution
Temperature measuring
range
0.1
-300 to 1100
-300.0 to 300.0
0.1
-300 to 900
-300.0 to 300.0
Resolution
1
0.1
1
0.1