Calibrating The Sitrans Rd200 (Cal) - Siemens SITRANS RD200 Operating Instructions Manual

Sitrans series
Hide thumbs Also See for SITRANS RD200:
Table of Contents

Advertisement

Error message (Err)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 1, allowing the
appropriate input signals to be applied.
The error message might be caused by any of the following conditions:
Input signal is not connected to the proper terminals or it is connected backwards
Wrong signal selection in Setup menu
Minimum input span requirements not maintained
Input 1 signal inadvertently applied to calibrate input 2.
Minimum input span
The minimum input span is the minimum difference between input 1 and input 2 signals
required to complete the calibration or scaling of the meter.
Input range
4 to 20 mA
±10 VDC
TC
RTD

Calibrating the SITRANS RD200 (CAL)

Recalibration is recommended at least every twelve months.
The meter can be calibrated to display the process in engineering units by applying the
appropriate input signal and following the calibration procedure.
The use of a calibrated signal source is strongly recommended to calibrate the meter.
To scale the meter without a signal source refer to
(ScAL)
on page 35.
Calibrate the meter with a signal source:
1.
Press Menu
2.
Press Up arrow
ProG
3.
When
4.
Press Up arrow
Calibrate Menu.
Page 36
Input 1 and input 2 span
0.40 mA
0.20 VDC
100°F (56°C)
50°F (28°C)
to enter Program Mode.
to scroll through choices.
is displayed, press Enter/Ack
CAL
until
is displayed. Press Enter/Ack
InP1
will be displayed.
SITRANS RD200 – OPERATING INSTRUCTIONS
Scaling the 4 to 20 mA analog input
.