Troubleshooting; Faults; No Good Pid Regeneration; Resetting The Pidbox Utility - ILUMEN PIDBOX Installation Manual

Pid solution, utility
Hide thumbs Also See for PIDBOX:
Table of Contents

Advertisement

Ilumen
10 T
ROUBLESHOOTING
10.1 F
AULTS
Lights readout
No lights visible
No lights visible
Blue light does not
burn during the night
while the red and
white lights are
burning.
Alternating lights red
and green.
Red light during the
day when in automatic
mode.
10.2 N
PID
O GOOD
If the modules are not regenerating or not regenerating fast enough you should check following
things:
 Check the grounding of the system. If necessary you should place additional
interconnections between the frames of the modules.
 Is the Ilumen PIDbox utility properly connected to the grid?
 Is the AC power properly connected (is its indication light burning)?
 Let an expert check if the problem you're having with the yield is caused by PID
10.3 R
ESETTING THE
The PIDbox utility can simply be reset by switching off the AC-power. Wait 20 seconds and
switch the AC-power back on.
If resetting does not help fixing your problem, please consult chapter 10.1 of this manual.
Installation Manual Ilumen PIDbox Utility v1.0
Fault
Product does not work
Product does work. The
front panel lights can be
defective
Product does not cure the
panels
The PIDbox is not in
automatic mode. The
position of the DC-circuit
breaker doesn't correspond
with the position it should
be in.
The power to the inverter
is interrupted during the
day
REGENERATION
PID
BOX UTILITY
Corrective action
Make sure the AC-power is connected
and AC voltage is present. Also make
sure that all the AC circuit breakers
inside the PIDbox utility are switched
on.
Please contact iLumen technical service.
This can have 2 reasons:
It takes about 1 minute to
activate the blue light after the
red light has turned on.
Earth connection between
PIDbox utility and the frame of
the modules is interrupted.
Check that the DC circuit breakers are in
automatic mode. Please check that the
plastic see-trough covers of the DC
circuit breakers are closed properly. A
black latch should click over the cover.
The DC switch has tripped. Reset the
DC-switch.
If the problem persists, please contact
iLumen technical service.
14