OLAR ARRAY AND INVERTER CONNECTIONS
When installing the PIDbox utility between the PV array and inverter always
switch off the DC switch of the inverter
1. Connect the positive DC cable coming from the first PV array. Connect it to the "PV in A+"
position.
2. Connect the negative DC cable coming from the first PV array. Connect it to the "PV in A-"
position.
3. Connect the positive DC cable coming from the second PV array (optional). Connect it to
the "PV in B+" position.
4. Connect the negative DC cable coming from the second PV array (optional). Connect it to
the "PV in B-" position.
5. Connect the "INV out A+" position to the positive side of the inverter of the first PV array
6. Connect the "INV out A-" position to the negative side of the inverter of the first PV array
7. Connect the "INV out B+" (optional) position to the positive side of the inverter of the
second PV array
8. Connect the "INV out B-" (optional) position to the negative side of the inverter of the
second PV array
If you work with inverters with multiple MPPT's you cannot mix the PV arrays
from multiple MPPT's.
The maximum current that can pass through the Ilumen PIDbox utility per channel
/ MPPT is indicated on the DC circuit breaker and on the type plate on the side of
the PIDbox utility. Make sure this is never exceeded.
Make sure the PV arrays are connected to the "PV in A" and "PV in B" side of the
Ilumen PIDbox utility, NEVER to the "INV out A" or "INV out B" side.