Chapter 2
The AADvance Safety Controller

Safety Features

Safety Configurations

18
The AADvance controller meets non-safety business requirements and SIL 2
and SIL 3 safety related system requirements. The system has comprehensive
built-in redundant capabilities that improve system availability.
The AADvance safety system features are:
• Easily transformed from a simplex non-safety system to a fault tolerant
safety related system.
• An AADvance platform provides a set of components that can be
configured to meet a range of safety and fault tolerance user
requirements within a single system such as - fault tolerant topologies
1oo1, 1oo2D and 2oo3.
• IEC 61508 certified, reviewed and approved for safety systems up to SIL
3 by independent certifying bodies.
• The scalable characteristics of the system enables independent safety
functions within the same system to be configured with different
architectures to meet a user specific safety and availability requirements.
• The main components that provide the safety architecture are the
processor and I/O modules; the remaining components provide secure
external interfaces and connectivity between the field elements and the
main components and add to the safety functionality.
• AADvance processor modules are designed to meet the requirements
for SIL 2 in a simplex configuration and SIL 3 in a dual or triplicated
configuration.
• Individual input modules are designed to meet the requirements for SIL
3 in simplex, dual or triple configurations.
• Individual output modules have been designed to meet the requirements
for SIL 3 in a simplex or dual configurations.
• Safe SIL 3 rated 'Black Channel' external communication over Ethernet.
An AADvance system supports the following safety configurations:
Fail-safe
I/O modules fail-safe in the most basic simplex system.
SIL 2
SIL 2 architectures for fail-safe low demand applications. All SIL 2
architectures can be used for energize or de-energize to trip applications.
• SIL 2 low demand architectures
• SIL 2 fail safe architectures
• SIL 2 fault tolerant input architectures
• SIL 2 triplicated input architectures
• SIL 2 fault tolerant output architectures
• SIL 2 fault tolerant input/output architectures
Rockwell Automation Publication ICSTT-RM448J-EN-P - April 2018