Adjust belt tension by loosing the motor mounting plate
front bolts and rear bolt (see Fig. 99) and slide the plate to-
wards the fan (to reduce tension) or away from the fan (to in-
crease tension). Ensure the blower shaft and motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts se-
curely when finished.
BELT DEFLECTION FORCE (LBS)
BELT
SMALLEST
UNNOTCHED
CROSS
SHEAVE
SECTION
DIAMETER
USED
3.0-3.6
3.7
A, AX
3.8-4.8
4.5
5.0-7.0
5.4
3.4-4.2
B, BX
4.4-5.6
5.3
5.8-8.6
6.3
Table 1
BELT CONDITION
TENSION FORCE IN BELT (LBS)
New
Used
Table 2
Fig. 98 — V-Belt Force Label
NOTCHED BELTS
BELTS
NEW
USED
NEW
5.5
4.1
6.8
5.0
8.0
5.7
4.9
7.9
7.1
10.5
9.4
8.5
12.6
100
80
BELT TENSION METHOD
Requires belt tension gauge that measures tension in belt
in units of lbs force.
MOUNTING
BOLTS (4)
Fig. 99 — Belt Drive Motor Mounting
6.1
7.4

Pre-Start and Start-Up

8.4
This completes the mechanical installation of the unit. Re-
7.2
fer to the unit's Service Manual for detailed Pre-Start and
Start-Up instructions. Download the latest versions from
HVAC Partners (www.hvacpartners.com).
63
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE