TB3 TERMINAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LEGEND
CCN
— Carrier Comfort Network (communication bus)
CMPSAFE — Compressor Safety
FILTER
— Filter Switch
FSD
— Fire Shutdown
IAQ
— Indoor Air Quality (CO
OAQ
— Outdoor Air Quality (CO
RH
— Relative Humidity
SFS
— Supply Fan Status
T55
— Space Temperature Sensor
T56
— Space Temperature Sensor
TB3 TERMINAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LEGEND
CCN
— Carrier Comfort Network (communication bus)
G
— Thermostat Fan
IAQ
— Indoor Air Quality (CO
OAQ
— Outdoor Air Quality (CO
RAT
— Return Air Temperature
RH
— Relative Humidity
W1
— Thermostat Heat Stage 1
W2
— Thermostat Heat Stage 2
Y1
— Thermostat Cool Stage 1
Y2
— Thermostat Cool Stage 2
Table 21 — Space Sensor Mode
FIELD CONNECTION
T55—SEN/T56—SEN
T55—SEN/T56—SEN
LOOP—PWR
IAQ—COM/OAQ—COM/RH—COM
CCN + (RED)
OAQ—SEN/RH—SEN
CCN Gnd (WHT)
AUX OUT(Power Exhaust)
CCN —(BLK)
)
2
)
2
Table 22 — Thermostat Mode
FIELD CONNECTION
LOOP—PWR
IAQ—COM/OAQ—COM/RH—COM
CCN + (RED)
OAQ—SEN/RH—SEN
CCN Gnd (WHT)
AUX OUT (Power Exhaust)
CCN — (BLK)
)
2
)
2
RMTOCC
CMPSAFE
T56—SET
FSD
SPS
IAQ—SEN
FILTER
RAT SEN
G
RAT SEN
Y1
—
Y2
W1
IAQ—SEN
W2
47
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
Analog, 24 vdc
Discrete, 24 vac
Analog, 4-20mA
Discrete, 24 vac
Analog, 4-20mA
Digital, 5 vdc
Analog, 4-20mA
Digital, 5 vdc
(Output) Discrete 24 vac
Digital, 5 vdc
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
—
Discrete, 24 vac
Analog, 24 vdc
Discrete, 24 vac
Analog, 4-20mA
Discrete, 24 vac
Analog, 4-20mA
Digital, 5 vdc
Analog, 4-20mA
Digital, 5 vdc
(Output) Discrete 24 vac
Digital, 5 vdc