Carrier WeatherMaster 50HC14 Installation Instructions Manual page 47

Single package rooftop cooling only unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

TB3 TERMINAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LEGEND
CCN
— Carrier Comfort Network (communication bus)
CMPSAFE — Compressor Safety
FILTER
— Filter Switch
FSD
— Fire Shutdown
IAQ
— Indoor Air Quality (CO
OAQ
— Outdoor Air Quality (CO
RH
— Relative Humidity
SFS
— Supply Fan Status
T55
— Space Temperature Sensor
T56
— Space Temperature Sensor
TB3 TERMINAL
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
LEGEND
CCN
— Carrier Comfort Network (communication bus)
G
— Thermostat Fan
IAQ
— Indoor Air Quality (CO
OAQ
— Outdoor Air Quality (CO
RAT
— Return Air Temperature
RH
— Relative Humidity
W1
— Thermostat Heat Stage 1
W2
— Thermostat Heat Stage 2
Y1
— Thermostat Cool Stage 1
Y2
— Thermostat Cool Stage 2
Table 21 — Space Sensor Mode
FIELD CONNECTION
T55—SEN/T56—SEN
T55—SEN/T56—SEN
LOOP—PWR
IAQ—COM/OAQ—COM/RH—COM
CCN + (RED)
OAQ—SEN/RH—SEN
CCN Gnd (WHT)
AUX OUT(Power Exhaust)
CCN —(BLK)
)
2
)
2
Table 22 — Thermostat Mode
FIELD CONNECTION
LOOP—PWR
IAQ—COM/OAQ—COM/RH—COM
CCN + (RED)
OAQ—SEN/RH—SEN
CCN Gnd (WHT)
AUX OUT (Power Exhaust)
CCN — (BLK)
)
2
)
2
RMTOCC
CMPSAFE
T56—SET
FSD
SPS
IAQ—SEN
FILTER
RAT SEN
G
RAT SEN
Y1
Y2
W1
IAQ—SEN
W2
47
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
Analog, 24 vdc
Discrete, 24 vac
Analog, 4-20mA
Discrete, 24 vac
Analog, 4-20mA
Digital, 5 vdc
Analog, 4-20mA
Digital, 5 vdc
(Output) Discrete 24 vac
Digital, 5 vdc
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24 vac
Analog (10k thermistor)
Discrete, 24 vac
Discrete, 24 vac
Analog, 24 vdc
Discrete, 24 vac
Analog, 4-20mA
Discrete, 24 vac
Analog, 4-20mA
Digital, 5 vdc
Analog, 4-20mA
Digital, 5 vdc
(Output) Discrete 24 vac
Digital, 5 vdc